5. On the connection cable, mark the terminal and the pin row to which the connection cable is

assigned. Use the supplied cable tie with caption field.

6. Write down the terminal assignment on the supplied supplementary sheet.

Connecting the Module Temperature Sensor

Additionally required accessories (not included in scope of delivery):

☐ 1 module temperature sensor
1 connection cable (see Section 6.3, page 30)

Requirements:

☐ The sensor must be technically suitable for connection to the temperature inputs (see Section 9,

page 84).

The connection cable must be prepared for connection to the multipole plug (see Section 6.5,

page 33).

Figure 14: Pin assignment for pin group Temperature input 2

Pin

Signal

Explanation

B1

GND

Shield ground

B2

I+

Current input

B3

V+

Voltage input

B4

V−

Voltage return

B5

I−

Current return

Procedure:

1. Connect the connection cable to the module temperature sensor (see the manual from

manufacturer). Trim the unneeded insulated conductors up to the cable shield and note down
the conductor colors.

2. For connection to the Cluster Controller using two-conductor connection technology, perform

the following steps:

• On the five-pole plug, unlock conductor entry 1 using a screwdriver and insert the

insulated conductor of the wire into the conductor entry.

6 Connection and Commissioning

SMA Solar Technology AG / SMA America, LLC

Installation Manual

ClusterController-IA-en-14