SMA CLUSTER CONTROLLER Installation User Manual
Page 34

1. Strip 40 mm (1.57 in) of cable sheath from the end of the connection cable to which the
multipole plug is to be attached.
2. Perform the following additional steps for the connection cables for the analog inputs, the
analog outputs and the temperature inputs:
• Trim the cable shield of the connection cable to 15 mm (0.59 in).
• Fold the surplus cable shield back over the
cable sheath.
• Press the shield clamp onto the cable shield.
The cable shield must be clamped under
the shield clamp as completely as possible.
• Depending on the number of connection cables, split the wire required for shielding into
pieces with a length of 40 mm (1.57 in).
• Remove 6 mm (0.24 in) of cable sheath
and strip 6 mm (0.24 in) of insulation at
both ends of the wire.
• Insert the insulated conductor at one end of
the wire into the ring terminal lug of the
shield clamp and crimp with a crimping
tool.
3. Trim unneeded insulated conductors flush with the cable sheath.
4. Strip off the conductor insulation by 6 mm (0.24 in).
6 Connection and Commissioning
SMA Solar Technology AG / SMA America, LLC
Installation Manual
ClusterController-IA-en-14
34