Terminal

Pin group

Pin

Function

X6

Analog current output 1

A1 to A3 Analog current output for feedback on

current active power limitation in grid
management services

Analog current output 2

A4 to A6 Analog current output for feedback on

current reactive power setpoint in grid
management services

Analog current output 3

B1 to B3

Analog current output for feedback on
the current total active system power (as
a percentage) based on the maximum
nominal system power

X7

Temperature input 1

A1 to A5 Analog input for connecting an external

temperature sensor

Temperature input 2

B1 to B5

Analog input for connecting a module
temperature sensor

X8

Analog current input 1

A1 to A4 Analog current input for connecting an ir-

radiation sensor or for measuring the ac-
tive power feed-in at the grid-connection
point

Analog current input 2

A5 to A8 Analog current input for active power lim-

itation in grid management services or for
measuring the active power feed-in at the
grid-connection point

Analog current input 3

B1 to B4

Analog current input for reactive power
setpoint in grid management services or
for measuring the active power feed-in at
the grid-connection point

Analog voltage input 4

B5 to B8

Analog voltage input for connecting a
sensor

X9, X10

1 to 8

Network ports for connection to the in-
verters (Speedwire)

X11, X12

Reserved for future applications

X13, X14

1 to 8

Network ports for connection to LAN

6.3

Cable Requirements

UV resistance of connection cables
Connection cables to be laid outdoors must be UV-resistant or routed in a UV-resistant cable
channel.