beautypg.com

2 digital setpoint signal, 1 connection options – SMA CLUSTER CONTROLLER Installation User Manual

Page 53

background image

Type of setpoint signal

Explanation

Analog signals

The setpoints are transmitted to the Cluster Controller as
analog current signals. Current signals from 0 mA to
20 mA can be transmitted for the active power limitation
and the reactive power setpoint.

Setpoint signal via Modbus client

The setpoints are transmitted via a Modbus client to the
network port X13 or X14 on the Cluster Controller (for in-
formation on Modbus configuration, see the Cluster Con-
troller user manual).

Closed-loop control

For Cluster Controller systems with self-consumption, the operating mode Closed-loop control is
used. In this operating mode, you can limit the active power fed in by the system at the grid-
connection point to a fixed percentage value. In addition to the total system power, the
Cluster Controller needs the measured actual value of the active power fed in at the grid-connection
point.

6.12.2 Digital Setpoint Signal

6.12.2.1 Connection Options

You have two options for each pin group on terminal X4:

• Connection of a signal source with potential-free relay contact

or

• Connection of a 24 V signal source with digital output signals

Connection of a signal source with potential-free relay contact

Figure 18: Connection of a signal source with potential-free relay contact (example)

6 Connection and Commissioning

SMA Solar Technology AG / SMA America, LLC

Installation Manual

53

ClusterController-IA-en-14