Connection

Cable requirements

Grounding

☐ Conductor cross-section: 2.5 mm

2

(14 AWG)

☐ Maximum cable length: 30 cm (11 in)

Voltage supply

☐ Number of insulated conductors: at least two
☐ Conductor cross-section: 0.2 mm

2

to 2.5 mm

2

(32 AWG to

14 AWG)

☐ Maximum cable length: 3 m (9.8 ft)

Digital inputs

☐ Number of insulated conductors: at least two
☐ Conductor cross-section: 0.2 mm

2

to 1.5 mm

2

(32 AWG to

16 AWG)

☐ Maximum cable length: 30 m (98 ft)

Digital outputs

☐ Number of insulated conductors: at least two
☐ Conductor cross-section: 0.2 mm

2

to 1.5 mm

2

(32 AWG to

16 AWG)

☐ Maximum cable length: 30 m (98 ft)

Analog inputs, analog out-
puts and temperature inputs
(wire)

☐ Conductor cross-section: 1.5 mm

2

(16 AWG)

☐ Cable length: 32 cm (12 in)

Analog Inputs
(connection cable)

☐ Number of insulated conductors: at least two
☐ Shielding: yes
☐ Conductor cross-section: 0.2 mm

2

to 1.5 mm

2

(32 AWG to

16 AWG)

☐ Maximum cable length: 30 m (98 ft)

Analog outputs
(connection cable)

☐ Number of insulated conductors: at least two
☐ Shielding: yes
☐ Conductor cross-section: 0.2 mm

2

to 1.5 mm

2

(32 AWG to

16 AWG)

☐ Maximum cable length: 3,000 m (9,840 ft)