Procedure:
1. Connect the connection cable to the remote terminal (see the manual from manufacturer). Trim
the unneeded insulated conductors up to the cable shield and note down the conductor colors.
2. When using the pin group Analog current output 3, perform the following steps to connect
the connection cable to the six-pole plug:
• Unlock conductor entry 3 with a screwdriver and insert the insulated conductor of the
wire into the conductor entry.
• Depending on the remote terminal and the pin assignment for the pin group Analog
current output 1, identify the conductor entries that are required for connecting the
connection cable.
• Release the required conductor entries using a screwdriver and insert the insulated
conductors into the conductor entries. Observe the pin assignment.
3. When using the pin group Analog current output 2, perform the following steps to connect
the connection cable to the six-pole plug:
• Unlock conductor entry 6 with a screwdriver and insert the insulated conductor of the
wire into the conductor entry.
• Depending on the remote terminal and the pin assignment for the pin group Analog
current output 2, identify the conductor entries that are required for connecting the
connection cable.
• Release the required conductor entries using a screwdriver and insert the insulated
conductors into the conductor entries. Observe the pin assignment.
4. When using the pin group Analog current output 3, perform the following steps to connect
the connection cable to the six-pole plug:
• Unlock conductor entry 3 with a screwdriver and insert the insulated conductor of the
wire into the conductor entry.
• Depending on the remote terminal and the pin assignment for the pin group Analog
current output 3, identify the conductor entries that are required for connecting the
connection cable.
• Release the required conductor entries using a screwdriver and insert the insulated
conductors into the conductor entries. Observe the pin assignment.
5. Insert the six-pole plug into the appropriate pin row in terminal X6:
• When using the pin group Analog current output 1 or Analog current output 2,
insert the six-pole plug into pin row A.
• When using the pin group Analog current output 3, insert the six-pole plug into pin
row B.
6. On the connection cable, mark the terminal and the pin row to which the connection cable is
assigned. Use the supplied cable tie with caption field.
7. Write down the terminal assignment on the supplied supplementary sheet.