beautypg.com

7 troubleshooting, 1 led states, 1 operation leds – SMA CLUSTER CONTROLLER Installation User Manual

Page 72: Troubleshooting, Led states, Operation leds, See section 7.1, 7troubleshooting

background image

7

Troubleshooting

7.1

LED States

7.1.1

Operation LEDs

Configuration of the Status LED (

):

The status LED can display the following statuses:

• Status of the Cluster Controller
• Status of the connected inverters
• Status of the system communication
• Status of the grid management services

In this document, the only states described below are those that the status LED can adopt during
commissioning (for a complete description of the states, see the Cluster Controller user manual).
If the status LED is not glowing green after commissioning, refer also to the event log of the
Cluster Controller to determine the precise cause of the error. The details of each error are logged
in the event log (see the Cluster Controller user manual).

LED

Status

Cause and corrective measure

All

off

The Cluster Controller is not connected to the voltage
supply.
Corrective measures:

• Connect the Cluster Controller to the voltage

supply (see Section 6.14, page 70).

The voltage supply is reverse-connected or the power
supply unit is defective.
Corrective measures:

• Ensure that the voltage supply is correctly

connected (see Section 6.14, page 70).

• If the voltage supply is connected correctly,

replace the power supply unit.

Power (

)

and
Status (

)

Power glowing
red, status glow-
ing yellow or red

The voltage supply is too low.
Corrective measures:

• Ensure that the connected voltage supply is

sufficient (see Section 6.14, page 70).

If the problem persists, contact the Service (see

Section 12, page 90).

Power (

)

glowing green

The start procedure is complete. The Cluster Con-
troller is ready for operation.

7 Troubleshooting

SMA Solar Technology AG / SMA America, LLC

Installation Manual

ClusterController-IA-en-14

72