Issue 10/06
3 Functions
MICROMASTER 440 Operating Instructions
6SE6400-5AW00-0BP0
79
3.5.1
50/60 Hz setting
The frequency setting made in the factory can be adapted to the North American
market, without requiring any parameterization using an operator panel or PC tool
using the DIP50/60 switch (refer to Fig. 3-21) under the I/O board (refer to the
Appendix C when removing the I/O board).
Rem
ov
e I
/O
board
DIP50/60
Fig. 3-21
DIP switch to change-over between 50/60 Hz
The switch determines the value of parameter P0100 corresponding to the
following diagram (refer to Fig. 3-22). Besides P0100 = 2, after the power supply
voltage has been switched-in, the DIP50/60 switch determines the 50/60 Hz setting
(value of parameter P0100).
P0100 = 2
?
P0100 = 0
P0100 = 2
P0100 = 1
P0100 = 2
?
P0100 = 1
?
yes
yes
no
no
yes
yes
no
no
Quick
commissioning
P0010 = 1
Power
cycle
DIP2 = OFF
?
Power in kW
Frequency 50 Hz
Power in kW
Frequency 60 Hz
Power in hp
Frequency 60 Hz
Fig. 3-22
Mode of operation of the DIP50/60 switch in conjunction with P0100