3.5.7.20 Diagnostic
parameters
r0035 CO: Motor temperature
Displays the measured motor temperature in °C.
r0036 CO: Frequency inverter utilization
Displays the frequency inverter utilization as a % referred to the overload. In so doing, the
value is calculated using the I
2
t model.
The I
2
t actual value relative to the maximum possible I
2
t value provides the level of
utilization.
r0052 CO/BO: Act. status word 1
Displays the first active status word (ZSW) of the frequency inverter (bit format) and can be
used to diagnose the inverter status.
r0054 CO/BO: Control word 1
Displays the first control word (STW) of the frequency inverter and can be used to display
the active commands.
r0063 CO: Actual frequency
Displays the actual frequency in Hz.
V/f
0
1,2
SLVC
(observer
model)
Encoder
P0400
P1300
160 ms
Frequency actual values:
Smoothed freq. actual value
Frequency actual value
Freq.act.value fr. the encoder
21,23
20,22
<20
0
P1300 = 21,23 and P0400 = 0 --> F0090
P0408
60
r0313
⋅
Smoothed speed act. value
r0313
60
r0022
r0021
r0063
r0061
r1079 CO: Selected frequency setpoint
Displays the selected frequency setpoint.
The following frequency setpoints are displayed:
r1078 total setpoint (HSW + ZUSW)
P1058 JOG frequency, clockwise
P1059 JOG frequency, counter-clockwise.
r1114 CO: Freq. setpoint after dir. ctrl.
Displays the setpoint (reference) frequency in Hz after the function block to reverse the
direction of rotation.
r1170 CO: : Frequency setpoint after RFG
Displays the total frequency setpoint (reference value) in Hz after the ramp-function
generator.