3 Functions
MICROMASTER 440 Operating Instructions
6SE6400-5AW00-0BP0
169
Contrary to "Direct selection + ON command", the ON command is only active if
the setting for the first 4 binary inputs is set to "Binary-coded selection + ON
command" or P0701 = P0702 = P0703 = P0704 = 17. The following is obtained
analog to the above example:
a) Standard method
→ P0701 = 17
b) BICO method
→ P0701 = 99, P1020 = 722.0, P1016 = 3
P1016
P0701 = 17 or P0701 = 99, P1020 = 722.0, P1016 = 3
DIN1
r0722.0
P1020
1
2,3
0
P0702 = 17 or P0702 = 99, P1021 = 722.1, P1017 = 3
P1017
DIN2
r0722.1
P1021
1
2,3
0
. .
. .
0 0 0
1
1 1 1
1
Festf requenz 15
-650.00 ... 650.00
[Hz]
P1015.D (65.00)
r1024
CO: Ist-
Festf req.
.
.
.
.
.
.
...
Festf requenz 1
-650.00 ... 650.00 [Hz]
P1001.D (0.00)
Fig. 3-50
Example for selecting FF1 via DIN1 and FF2 via DIN2 using the binary-coded
method