Watson-Marlow MM440 User Manual
Page 266

5 MICROMASTER 440 specifications
Issue 10/06
MICROMASTER 440 Operating Instructions
266
6SE6400-5AW00-0BP0
Table 5-4
Data for braking resistors
I
DC_max
for Frame Size
Rated voltage
V
DC_max
A B
C
D E F
230 V
410 - 420 V
2,33 A
(180
Ω)
6,18 A
(68
Ω)
10,77 A (39
Ω)
15,56 A (27
Ω)
41,0 A
(10
Ω)
60,3 A
(6,8
Ω)
124,2 A
(3,3
Ω)
400 V
820 - 840 V
2,15 A
(390
Ω)
5,25 A
(160
Ω)
15 A
(56
Ω)
30,4 A
(27
Ω)
54,7 A
(15
Ω)
100,0 A
(8,2
Ω)
575 V
1020 V
-
-
8,5 A (120
Ω)
12,4 A (82
Ω)
26,2 A
(39
Ω)
37,8 A
(27
Ω)
85,0 A
(12
Ω)
Table 5-5
MICROMASTER 440 Specifications
In order that the system is in compliance with UL, UL-certified fuses must be
used with the appropriate rated current.
Input voltage range
1 AC 200 V – 240 V, ± 10 %
(with built in Class A Filter)
Order No.
6SE6440- 2AB11
-2AA1
2AB12
-5AA1
2AB13
-7AA1
2AB15
-5AA1
2AB17
-5AA1
2AB21
-1BA1
2AB21
-5BA1
2AB22
-2BA1
2AB23
-0CA1
[kW]
0.12 0.25 0.37 0.55
0.75 1.1 1.5 2.2 3.0
Output Rating (CT)
[hp]
0.16
0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0
Output Power
[kVA]
0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0
CT Input Current 1)
[A]
1.8 3.2 4.6 6.2 8.2 11.0
14.4
20.2
35.5
CT Output Current
[A]
0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4
13.6
Fuse [A]
10 10 10 16 16 20 20 32 40
Recommended 3NA
3803 3803 3803 3805 3805 3807 3807 3812 3817
for UL specified
* * * * * * * * *
[mm
2
]
1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0 6.0
Input Cable Min.
[awg]
18 18 18 16 16 14 14 12 10
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
Input Cable Max.
[awg]
14 14 14 14 14 10 10 10 8
[mm
2
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5
Output Cable Min.
[awg]
18 18 18 18 18 18 18 18 16
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
Output Cable Max.
[awg]
14 14 14 14 14 10 10 10 8
[kg]
1.3
1.3 1.3 1.3 1.3 3.4 3.4 3.4 5.7
Weight
[lbs]
2.9
2.9 2.9 2.9 2.9 7.5 7.5 7.5 12.5
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 2 % referred to the rated drive converter power and a rated line supply voltage
of 240 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America