13 free function blocks (ffb) – Watson-Marlow MM440 User Manual
Page 191

Issue 10/06
3 Functions
MICROMASTER 440 Operating Instructions
6SE6400-5AW00-0BP0
191
3.13
Free function blocks (FFB)
Parameter range:
P2800 – P2890
Warnings -
Faults -
Function chart number:
FP4800 – FP4830
Cycle time:
128 ms
For many applications, interlocking logic is required in order to control (open-loop)
the drive inverter. This interlocking logic couples several states (e.g. access
control, plant/system state) to form a control signal (e.g. ON command). Previously
this was implemented using either a PLC or relays. This represented additional
costs for the plant or system. In addition to logic operations, increasingly, arithmetic
operations and storage elements are required in drive inverters which generate a
new unit from several physical quantities. This simplified PLC functionality is
integrated in MICROMASTER 440 using the freely programmable function blocks
(FFB).
The following function blocks are integrated in MICROMASTER 440:
Table 3-31
Free function blocks
No. Type
Example
3
AND
AND 1
P2800 P2801[0]
A
B
C
&
P2810
r2811
A
B
C
0
0
0
0
1
0
1
0
0
1
1
1
Index0
Index1
3
OR
OR 1
A
B
C
P2816
r2817
A
B
C
0
0
0
0
1
1
1
0
1
1
1
1
1
P2800 P2801[3]
Index0
Index1
3
XOR
XOR 1
A
B
C
P2822
r2823
A
B
C
0
0
0
0
1
1
1
0
1
1
1
0
1
=
P2800 P2801[6]
Index0
Index1
3
NOT
NOT 1
P2828
r2829
1
C
A
A
C
0
1
1
0
P2800 P2801[9]
Index0