1 universal serial interface (uss) – Watson-Marlow MM440 User Manual
Page 146

3 Functions
Issue 10/06
MICROMASTER 440 Operating Instructions
146
6SE6400-5AW00-0BP0
NOTE
¾
A communications (CB) module as well as a programming / operator unit can
be simultaneously connected to the COM link interface via terminals 29/30
(USS). This is the reason that the communications module has priority over
USS. In this case, the USS node (USS station) via the COM link is de-activated.
¾
Contrary to PROFIBUS, the RS485 port (terminals 29/30) is not optically isolated
(not floating). When installing the system, it must be ensured that EMC faults do
not result in communication failures or damage to the RS485 drivers.
3.7.1
Universal serial interface (USS)
Parameter range:
P2009 – r2037
Significance
COM link
BOP link
USS basic setting
USS baud rate
P2010[0]
P2010[1]
USS
address
P2011[0]
P2011[1]
USS-PZD
length
P2012[0]
P2012[1]
USS-PKW
length
P2013[0]
P2013[1]
PZD data
Received
data
r2018[8]
r2015[8]
Received control word 1
r2036
r2032
Received control word 2
r2037
r2033
Sent
data
P2019[8]
P2016[8]
Sent status word 1
r0052
r0052
Sent status word 2
r0053
r0053
Alarms: ---
Faults: F0071,
F0072
Function chart number: FP2500, FP2510, FP2600, FP2610
Features:
− electrical features: Not electrically isolated
USS at the BOP link with PC-
converter connecting set
Not electrically isolated
USS at COM link
(terminals 29 /30)
− cycle time (MM440): 8 ms
(process data PZD)
Background (parameter ID value PKW)