Watson-Marlow MM440 User Manual
Page 270

5 MICROMASTER 440 specifications
Issue 10/06
MICROMASTER 440 Operating Instructions
270
6SE6400-5AW00-0BP0
Input voltage range
3 AC 380 V – 480 V. ± 10 %
(Unfiltered)
Order No.
6SE6440- 2UD13
-7AA1
2UD15
-5AA1
2UD17
-5AA1
2UD21
-1AA1
2UD21
-5AA1
2UD22
-2BA1
2UD23
-0BA1
2UD24
-0BA1
2UD25
-5CA1
2UD27
-5CA1
[kW]
0.37 0.55 0.75 1.1
1.5 2.2 3.0 4.0 5.5 7.5
Output Rating (CT)
[hp]
0.5 0.75 1.0 1.5 2.0 3.0 4.0 5.0 7.5 10.0
Output Power
[kVA]
0.9 1.2 1.6 2.3 3.0 4.5 5.9 7.8 10.1
14.0
CT Input Current 1)
[A]
2.2 2.8 3.7 4.9 5.9 7.5 10.0
12.8
15.6
22.0
CT Output Current
[A]
1.3 1.7 2.2 3.1 4.1 5.9 7.7 10.2
13.2
19.0
VT Input Current 1)
[A]
− − − − − − − −
17.3 23.1
VT-Output Current
[A]
− − − − − − − −
19.0 26.0
Fuse [A]
10 10 10 10 10 16 16 20 20 32
Recommended 3NA
3803 3803 3803 3803 3803 3805 3805 3807 3807 3812
for UL specified
*
*
*
*
*
*
*
*
*
*
[mm
2
]
1.0 1.0 1.0 1.0 1.0 1.5 1.5 2.5 2.5 4.0
Input Cable Min.
[awg]
18 18 18 18 18 16 16 14 14 12
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
10.0
Input Cable Max.
[awg]
14 14 14 14 14 10 10 10 8 8
[mm
2
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 2.5 4.0
Output Cable Min.
[awg]
18 18 18 18 18 18 18 18 14 12
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
10.0
Output Cable Max.
[awg]
14 14 14 14 14 10 10 10 8 8
[kg]
1.3 1.3 1.3 1.3 1.3 3.3 3.3 3.3 5.5 5.5
Weight
[lbs]
2.9 2.9 2.9 2.9 2.9 7.3 7.3 7.3 12.1
12.1
Order No.
6SE6440- 2UD31
-1CA1
2UD31
-5DA1
2UD31
-8DA1
2UD32
-2DA1
2UD33
-0EA1
2UD33
-7EA1
2UD34
-5FA1
2UD35
-5FA1
2UD37
-5FA1
[kW]
11.0 15.0 18.5 22.0 30.0 37.0 45.0 55.0 75.0
Output Rating (CT)
[hp]
15.0 20.0 25.0 30.0 40.0 50.0 60.0 75.0 100.0
Output Power
[kVA]
19.8 24.4 29.0 34.3 47.3 57.2 68.6 83.8 110.5
CT Input Current 1)
[A]
23.1 33.8 37.0 43.0 59.0 72.0 87.0 104.0
139.0
CT Output Current
[A]
26.0 32.0 38.0 45.0 62.0 75.0 90.0 110.0
145.0
VT Input Current 1)
[A]
33.8 37.0 43.0 59.0 72.0 87.0 104.0
139.0
169.0
VT-Output Current
[A]
32.0 38.0 45.0 62.0 75.0 90.0 110.0
145.0
178.0
Fuse [A]
35 50 63 80 100 125 160 200 250
Recommended 3NA
3814 3820 3822 3824 3830 3832 3836 3140 3144
for UL specified
3NE
*
1817-0
1818-0
1820-0
1021-0
1022-0
1224-0
1225-0
1227-0
[mm
2
]
6.0 10.0 10.0 16.0 25.0 25.0 35.0 70.0 95.0
Input Cable Min.
[awg]
10 8 8 6 3 3 2 2/0
3/0
[mm
2
] 10.0 35.0 35.0 35.0 35.0 35.0 150.0
150.0
150.0
Input Cable Max.
[awg]
8 2 2 2 2 2
300
300
300
[mm
2
]
6.0 10.0 10.0 16.0 25.0 25.0 35.0 70.0 95.0
Output Cable Min.
[awg]
10 8 8 6 3 3 2 2/0
3/0
[mm
2
] 10.0 35.0 35.0 35.0 35.0 35.0 150.0
150.0
150.0
Output Cable Max.
[awg]
8 2 2 2 2 2
300
300
300
[kg]
5.5 16.0 16.0 16.0 20.0 20.0 56.0 56.0 56.0
Weight
[lbs]
12.1 35.0 35.0 35.0 44.0 44.0 123.0
123.0
123.0
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 2 % referred to the rated drive converter power and a rated line supply voltage
of 400 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America