Watson-Marlow MM440 User Manual
Page 268

5 MICROMASTER 440 specifications
Issue 10/06
MICROMASTER 440 Operating Instructions
268
6SE6400-5AW00-0BP0
Input voltage range
3 AC 200 V – 240 V. ± 10 %
(Unfiltered)
Order No.
6SE6440- 2UC11
-2AA1
2UC12
-5AA1
2UC13
-7AA1
2UC15
-5AA1
2UC17
-5AA1
2UC21
-1BA1
2UC21
-5BA1
2UC22
-2BA1
2UC23
-0CA1
[kW]
0.12 0.25 0.37 0.55
0.75 1.1 1.5 2.2 3.0
Output Rating (CT)
[hp]
0.16
0.33 0.5 0.75 1.0 1.5 2.0 3.0 4.0
Output Power
[kVA]
0.4 0.7 1.0 1.3 1.7 2.4 3.2 4.6 6.0
CT Input Current 1)
[A]
1.1 1.9 2.7 3.6 4.7 6.4 8.3 11.7
15.6
CT Output Current
[A]
0.9 1.7 2.3 3.0 3.9 5.5 7.4 10.4
13.6
Fuse [A]
10 10 10 16 16 20 20 25 25
Recommended
3NA
3803 3803 3803 3805 3805 3807 3807 3810 3810
for UL specified
* * * * * * * * *
[mm
2
]
1.0 1.0 1.0 1.5 1.5 2.5 2.5 2.5 4.0
Input Cable Min.
[awg]
18 18 18 16 16 14 14 14 12
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
Input Cable Max.
[awg]
14 14 14 14 14 10 10 10 8
[mm
2
]
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5
Output Cable Min.
[awg]
18 18 18 18 18 18 18 18 16
[mm
2
]
2.5 2.5 2.5 2.5 2.5 6.0 6.0 6.0 10.0
Output Cable Max.
[awg]
14 14 14 14 14 10 10 10 8
[kg]
1.3 1.3 1.3 1.3 1.3 3.3 3.3 3.3 5.5
Weight
[lbs]
2.9 2.9 2.9 2.9 2.9 7.3 7.3 7.3 12.1
Order No.
6SE6440- 2UC24-
0CA1
2UC25-
5CA1
2UC27-
5DA1
2UC31-
1DA1
2UC31-
5DA1
2UC31-
8EA1
2UC32-
2EA1
2UC33-
0FA1
2UC33-
7FA1
2UC34-
5FA1
[kW]
4.0 5.5 7.5 11.0
15.0 18.5 22.0 30.0 37.0 45.0
Output Rating (CT)
[hp]
5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0
Output Power
[kVA]
7.7 9.6 12.3 18.4 23.7 29.8 35.1 45.6 57.0 67.5
CT Input Current 1)
[A]
19.7 26.5 34.2 38.0 50.0 62.0 71.0 96.0 114.0
135.0
CT-Output Current
[A]
17.5 22.0 28.0 42.0 54.0 68.0 80.0 104.0
130.0
154.0
VT Input Current 1)
[A]
28.3 34.2 38.0 50.0 62.0 71.0 96.0 114.0
135.0
164.0
VT-Output Current
[A]
22.0 28.0 42.0 54.0 68.0 80.0 104.0
130.0
154.0
178.0
Fuse [A]
32 35 50 80 80 100 125 200 200 250
Recommended
3NA
3812 3814 3820 3824 3824 3830 3832 3140 3142 3144
for UL specified
3NE
* *
1817-0 1820-0 1820-0 1021-0 1022-0 1225-0 1225-0 1227-0
[mm
2
] 4.0 4.0 10.0 16.0 16.0 25.0 25.0 70.0 70.0 95.0
Input Cable Min.
[awg]
12
12 8 6 6 3 3 2/0
2/0
3/0
[mm
2
] 10.0 10.0 35.0 35.0 35.0 35.0 35.0 150.0
150.0
150.0
Input Cable Max.
[awg]
8
8
2
2
2
2
2 300 300 300
[mm
2
] 4.0 4.0 10.0 16.0 16.0 25.0 25.0 50.0 70.0 95.0
Output Cable Min.
[awg]
12
12 8 6 6 3 3 1/0
2/0
3/0
[mm
2
] 10.0 10.0 35.0 35.0 35.0 35.0 35.0 150.0
150.0
150.0
Output Cable Max.
[awg]
8
8
2
2
2
2
2 300 300 300
[kg]
5.5 5.5 17.0 16.0 16.0 20.0 20.0 55.0 55.0 55.0
Weight
[lbs]
12.1 12.1 37.0 35.0 35.0 44.0 44.0 121.0
121.0
121.0
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
supply V
k
= 2 % referred to the rated drive converter power and a rated line supply voltage
of 240 V without line commutating reactor.
* UL listed fuses such as Class NON from Bussmann are required for use in America