3 Functions
Issue 10/06
MICROMASTER 440 Operating Instructions
136
6SE6400-5AW00-0BP0
Parameter P0725 is used to define as to whether digital inputs DIN1 - DIN6 are
logical "1" when appropriately connected to 0 V or 24 V. The logical states of the
digital inputs can be de-bounced using P0724 and read-out using parameter r0722
(BICO monitoring parameter). Further, this parameter is used to parameterize
BICO for the digital inputs (refer to BICO parameterization in the following Section).
P0701 – P0706 (digital inputs 1–6) or P0707 – P0708 (analog inputs 1-2)
The possible settings of the individual inputs are listed in Table 3-11.
Table 3-11
Parameters P0701 – P0706
Parameter value
Significance
0
Digital input disabled
1 ON
/
OFF1
2
ON+reverse / OFF1
3
OFF2 – coast to standstill
4
OFF3 – quick ramp-down
9 Fault
acknowledge
10 JOG
right
11 JOG
left
12 Reverse
13
MOP up (increase frequency)
14
MOP down (decrease frequency)
15
Fixed setpoint (direct selection)
16
Fixed setpoint (direct selection + ON)
17
Fixed setpoint (binary-coded selection + ON)
25
Enable DC braking
29 External
trip
33
Disable additional frequency setpoint
99
Enable BICO parameterization
Example:
An ON/OFF1 command should be realized using digital input DIN1.
P0700 = 2
Control enabled via terminal strip (digital inputs)
P0701 = 1
ON/OFF1 via digital input 1 (DIN1)
NOTE
If an analog input (refer to Fig. 3-33) has been configured as digital input, then the
following limit values apply:
< 1.7 V DC
→ "0"
> 3.9 V DC
→ "1"