Watson-Marlow MM440 User Manual
Page 264

5 MICROMASTER 440 specifications
Issue 10/06
MICROMASTER 440 Operating Instructions
264
6SE6400-5AW00-0BP0
Table 5-2
Dimensions, required cooling air flow and tightening torques for power terminals
Frame
Size
Dimensions
Required cooling air flow
Tightening torque for
power connections
mm
73
× 173 × 149
l/s 4.8 Nm 1.1
A
WxHxD
inch
2.87
× 6.81 × 5.87
CFM 10.2
mm
149
× 202 × 172
l/s 24 Nm 1.5
B
WxHxD
inch
5.87
× 7.95 × 6.77
CFM 51
mm
185
× 245 × 195
l/s 54.9 Nm 2.25
C
WxHxD
inch
7.28
× 9.65 × 7.68
CFM 116.3
mm
275
× 520 × 245
l/s
2
× 54.9
Nm 10
(max.)
D
WxHxD
inch
10.82
× 20.47 × 9.65
CFM
2
× 116.3
mm
275
× 650 × 245
l/s
2
× 54.9
Nm 10
(max.)
E
WxHxD
inch
10.82
× 25.59 × 9.65
CFM
2
× 116.3
mm
350
× 850
Height with filter 1150
l/s 150 Nm
50
F
WxHxD
inch
13.78
× 33.46 × 12.60
Height with filter 45.28
CFM 317.79
mm
326
× 1400 × 356
l/s 225 Nm 25
FX
WxHxD
inch
12.80
× 55.12 × 12.83 CFM 478.13
mm
326
× 1533 × 545
l/s 440 Nm 25
GX
WxHxD
inch
12.80
× 60.35 × 21.46 CFM 935