Generator overvoltage protection, Soft-start function, Analog (auxiliary) input – Basler Electric BE2000E User Manual

Page 77: Metering

background image

9287500995 Rev B

69

Generator Overvoltage Protection

Pickup
Range ......................................... 105 to 120% of setpoint
Increment ................................... 1.0%

Time Delay
Fixed Setting .............................. 0.75 seconds

Soft-Start Function

Time Adjust Range ..................... 1 to 120 seconds
Increment ................................... 1 second

Analog (Auxiliary) Input

Voltage Range ...........................

–3 Vdc to +3 Vdc

Setpoint Range ..........................

–30% to +30% shift

Burden ........................................ 1 k

Terminals.................................... A, B

Metering

Accuracy of all metering values assumes 25

°C, 50/60 Hz and less than 20% THD.

Generator Voltage
Range ......................................... 10 V to 79 kV
Accuracy..................................... 0.5%

Generator Current
Range ......................................... 0.1 to 5,000 A (5 A CTs)
Accuracy..................................... 0.5%

Frequency
Range ......................................... 40 to 65 Hz
Accuracy..................................... 0.2 Hz

Field Voltage
Range ......................................... 0 to 200 Vdc
Accuracy..................................... 5.0%

Field Current
Range ......................................... 0 to 8.0 Adc
Accuracy..................................... 0.5%

Power (Apparent, Real and Reactive)
Range ......................................... 0 to 99 MVA, MW and Mvar
Accuracy..................................... 3.0%

Power Factor
Range .........................................

–1.0 to –0.6, +0.6 to +1.0

Accuracy..................................... 0.02

Phase Angle
Range ......................................... 0 to 360

°

Accuracy..................................... 2

°

BE2000E

Specifications