AVR Operating Mode

Adjustment Range ...................... See generator voltage sensing
Voltage Regulation .....................

±0.25% over load range at rated PF and constant generator frequency

Temperature Drift .......................

±0.5% for a 40°C change

Response Time ..........................

≤ 1 cycle

Underfrequency (V/Hz)
Characteristic ............................. Slope from 1 to 3 PU is adjustable in 0.01 increments
Range ......................................... 40 to 65 Hz
Increment ................................... 0.01 Hz

FCR (Manual) Operating Mode

Adjustment Range ...................... 0 to 3 Adc
Increment ................................... 0.01 A

Var Operating Mode

Adjustment Range ...................... 100% to –100%
Increment ................................... 0.1%

PF Operating Mode

Adjustment Range ...................... 0.6 lead to 0.6 lag
Increment ................................... 0.001

Parallel Compensation

Modes ......................................... Reactive Droop and Reactive Differential (cross-current)

*

Droop
Adjustment Range ...................... 0 to 10%
Increment ................................... 0.01%

* Burden can exceed 1 VA if external resistors are added to the CT circuit.

Communication Port

Interface ..................................... Full Duplex RS-232
Connection ................................. DB-9 connector on rear panel
Baud ........................................... 4800
Data Bits ..................................... 8
Parity .......................................... None
Stop Bit ....................................... 1

Field Overvoltage Protection

Pickup ......................................... 0 to 250 Vdc
Time Delay ................................. 15 seconds (fixed)

Field Overcurrent Protection

Pickup
Adjustment Range ...................... 0 to 7.5 Adc
Increment ................................... 0.001 Adc

Time Delay
Adjustment Range ...................... 0 to 10 seconds
Increment ................................... 1 second

Specifications

BE2000E