Basler Electric BE2000E User Manual
Page 17

9287500995 Rev B
9
Table 10. Power Factor Control Adjustment Ranges
Power Factor Control Adjust – LED #6 Blinking Slowly
Maximum Adjustment Range: +0.6 (lag) to –0.6 (lead)
Increment: 0.01
LED
Minimum Value †
Maximum Value †
12
0.66
0.60
11
0.73
0.67
10
0.80
0.74
9
0.86
0.81
8
0.93
0.87
7
1.0
0.94
6
-0.94
-0.99
5
-0.87
-0.93
4
-0.80
-0.86
3
-0.74
-0.79
2
-0.67
-0.73
1
-0.60
-0.66
† Minimum and maximum values may differ from the Table 10 values if
the value has been changed in BESTCOMS-BE2000E software.
BESTCOMS-BE2000E has 0.001 resolution compared to the 0.01
resolution of the HMI.
Table 11. Underfrequency Adjustment Ranges
Underfrequency Adjust – LED #7 Blinking Slowly
Maximum Adjustment Range: 40 to 65 Hz
Increment: 0.1 Hz
LED
Minimum Value
Maximum Value
12
63.0
65.0
11
60.9
62.9
10
58.8
60.8
9
56.7
58.7
8
54.6
56.6
7
52.5
54.5
6
50.5
52.4
5
48.4
50.4
4
46.3
48.3
3
44.2
46.2
2
42.1
44.1
1
40.0
42.0
BE2000E
Human-Machine Interface