Table 10. Power Factor Control Adjustment Ranges

Power Factor Control Adjust – LED #6 Blinking Slowly

Maximum Adjustment Range: +0.6 (lag) to –0.6 (lead)

Increment: 0.01

LED

Minimum Value

Maximum Value

12

0.66

0.60

11

0.73

0.67

10

0.80

0.74

9

0.86

0.81

8

0.93

0.87

7

1.0

0.94

6

-0.94

-0.99

5

-0.87

-0.93

4

-0.80

-0.86

3

-0.74

-0.79

2

-0.67

-0.73

1

-0.60

-0.66

Minimum and maximum values may differ from the Table 10 values if

the value has been changed in BESTCOMS-BE2000E software.
BESTCOMS-BE2000E has 0.001 resolution compared to the 0.01
resolution of the HMI.

Table 11. Underfrequency Adjustment Ranges

Underfrequency Adjust – LED #7 Blinking Slowly

Maximum Adjustment Range: 40 to 65 Hz

Increment: 0.1 Hz

LED

Minimum Value

Maximum Value

12

63.0

65.0

11

60.9

62.9

10

58.8

60.8

9

56.7

58.7

8

54.6

56.6

7

52.5

54.5

6

50.5

52.4

5

48.4

50.4

4

46.3

48.3

3

44.2

46.2

2

42.1

44.1

1

40.0

42.0