Table 8. On-Line Operating Mode (AVR (OFF)/VAR/PF) Select

AVR (OFF) / VAR / PF Select – LED #5 Blinking Slowly

LED

MODE

12

N/A

11

N/A

10

N/A

9

N/A

8

N/A

7

N/A

6

N/A

5

N/A

4

N/A

3

Var

2

PF

1

AVR

Table 9. VAR Control Adjustment Ranges

VAR Control Adjust – LED #6 Blinking Slowly

Maximum Adjustment Range:

−100% (absorb) to +100% (generate)

Increment: 1.0%

LED

Minimum Value

*

Maximum Value

*

12

84

100

11

67

83

10

51

66

9

34

50

8

17

33

7

1

16

6

-16

0

5

-33

-17

4

-49

-34

3

-66

-50

2

-83

-67

1

-100

-84

* Minimum and maximum values may differ from the Table 9 values if

the value has been changed in BESTCOMS

™-BE2000E software.

BESTCOMS-BE2000E has 0.5 percent resolution compared to the
1.0 percent resolution of the HMI.