10
9287500995 Rev B
Table 12. Droop Adjustment Ranges
Droop Adjust – LED #8 Blinking Slowly
Adjustment Range: 0 to 10%
Increment: 0.25%
LED
Minimum Value
*
Maximum Value
*
12
9.25
10.00
11
8.5
9.00
10
7.75
8.25
9
6.75
7.50
8
6.00
6.50
7
5.25
5.75
6
4.25
5.00
5
3.5
4.00
4
2.75
3.25
3
1.75
2.5
2
1
1.5
1
0
0.75
* Minimum and maximum values may differ from the Table 12 values if
the value has been changed in BESTCOMS-BE2000E software.
BESTCOMS-BE2000E has 0.01% resolution compared to the 0.25
percent resolution of the HMI.
Table 13. Stability Range Selection Settings
Stability Range Select – LED #9 Blinking Slowly
Adjustment Range per LED: 1
Frame/Poles
LED
Range Selected
12
N/A
11
N/A
10
N/A
9
N/A
Programmable
8
21
1,000/6
7
7
740/6
6
6
1,000/4
5
5
740/4
4
4
570/4
3
3
430/4
2
2
360/4
1
1
Human-Machine Interface
BE2000E