BE2000E electrical and physical specifications are listed in the following paragraphs. The adjustment
increments shown apply to the PC software. Adjustment increments for the Front Panel Controls are
listed in the Human-Machine Interface chapter.

Operating Power

Single-Phase .............................. 180 to 240 Vac
Frequency Range ....................... 120 to 300 Hz
Burden ........................................ 330 VA
Terminals.................................... 3, 4

Generator Voltage Sensing

Type ........................................... 1-phase/3-phase, 4 ranges, 50/60 Hz
Terminals.................................... E1, E2, E3
Burden ........................................ <1 VA per phase
Range 1 ...................................... 120 Vac (100 to 140 Vac)
Range 2 ...................................... 240 Vac (200 to 280 Vac)
Range 3 ...................................... 480 Vac (400 to 560 Vac)
Range 4 ...................................... 600 Vac

Generator Current Sensing

Type ........................................... 1-phase (BØ), 50/60 Hz
Rating ......................................... 5 Aac maximum continuous
Burden ........................................ <0.1 VA
Terminals.................................... CT1, CT2

Contact Input Circuits

Type ........................................... Dry Contact
Interrogation Voltage .................. 13 Vdc

Terminals
Unit/Parallel Control ................... 52L, 52M
Raise .......................................... 6U, 7
Lower .......................................... 6D, 7
var/PF Enable ............................ 52J, 52K

Common Alarm Output

Type ........................................... Form A
Rated Load ................................. 7 Aac/7 Adc continuous
Make ........................................... 30 Aac/30 Adc, carry for 0.2 seconds
Break .......................................... 7 Aac/0.1 Adc
Operating Voltage ...................... 240 Vac/250 Vdc maximum
Terminals.................................... AL1, AL2

Field Output

Continuous Rating ...................... 75 Vdc, 3.0 Adc

10 Second Forcing Rating
200 Vac Power Input: ................. 150 Vdc, 7.5 Adc
Field Resistance: ........................ 18

Ω minimum

Terminals:................................... F+, F

BE2000E

Specifications