Power (Field) Output

The field output terminals for connection to the generator exciter field are labeled F+ and F

–.

Relay Output

The common alarm relay output contact may be accessed at the terminals labeled AL1 and AL2. The
relay output is normally open.

Communication Port

The RS-232 port on the rear panel uses a DB-9 female connector. Figure 7 illustrates the pin
assignments of the communication port and Table 17 identifies the RS-232 connector pin functions. A
standard communication cable terminated with a DB-9 male connector is used for PC or hand-held
computer interface with the BE2000E as shown in Figure 8.

Figure 7. Communication Port Pin Assignments

Table 17. Communication Port Pin Functions

Pin

Function

Name

Direction

1

N/C

----

N/A

2

Transmit Data

TXD

From BE2000E

3

Receive Data

RXD

To BE2000E

4

N/C

----

N/A

5

Signal Ground

GND

N/A

6

N/C

----

N/A

7

N/C

----

N/A

8

N/C

----

N/A

9

N/C

----

N/A