Basler Electric BE2000E User Manual
Page 50

42
9287500995 Rev B
Figure 24. Control Gain Screen
AVR/FCR - Integral Gain KI. This setting selects the integral constant (KI) stability parameter. The
BE2000E supplies a value that is equivalent to KI multiplied by the integral of the error between the
voltage setpoint and the actual generator output voltage. KI values of 0 to 2,000 may be entered in
increments of 0.01.
Increasing the value of KI decreases the time required to reach steady state.
AVR/FCR - Derivative Gain KD. This setting selects the derivative constant (KD) stability parameter. The
BE2000E provides an output value that is equivalent to KD multiplied by the derivative of the error
between the voltage setpoint and the actual generator output voltage. KD values of 0 to 1,000 may be
entered in increments of 0.01.
Increasing the value of KD reduces transient response ringing.
AVR/FCR - Loop Gain Kg=>AVR. This setting adjusts the loop-gain level of the PID algorithm for AVR.
Loop Gain values of 0.5 to 4.5 may be entered for AVR operation in increments of 0.01.
AVR/FCR - Loop Gain Kg=>FCR. This setting adjusts the loop-gain level of the PID algorithm for FCR.
Loop Gain values of 0 to 1,000 may be entered FCR operation in increments of 0.01.
VAR/PF - PF Integral Gain KI. This setting adjusts the integral gain and determines the characteristic of
the BE2000E dynamic response to a changed PF setting. PF KI values of 0 to 1,000 may be entered in
increments of 0.01.
VAR/PF - Var Integral Gain KI. This setting adjusts the integral gain and determines the characteristic of
the BE2000E dynamic response to a changed var setting. Var KI values of 0 to 1,000 may be entered in
increments of 0.01.
VAR/PF - VAR<=Loop Gain Kg=>PF. This setting adjusts the loop-gain level of the PI algorithm for var or
power factor control. Loop Gain values of 0 to 1,000 may be entered for var and power factor operation in
increments of 0.01.
OEL - Integral Gain KI. This setting controls the rate at which the BE2000E responds during an
overexcitation event. KI values of 0 to 1,000 may be entered in increments of 0.01.
OEL - Loop Gain Kg. This setting adjusts the loop-gain level of the PID algorithm for the over-excitation
limiting function. Loop Gain values of 0 to 1,000 may be entered in increments of 0.01.
BESTCOMS
™ Software
BE2000E