Figure 27. Analysis Screen, FCR Tab
Field Current Step Response - Increment of FCR Setpoint (A). These two fields indicate the increase that
occurs to the FCR setpoint when the corresponding Increment button is clicked. The "% increase" field is
used to set and indicate the percentage that the FCR setpoint is increased when the Increment button is
clicked. The "FCR Setpoint =" field indicates the value of current that corresponds to the "% increase"
field. Any setpoint value within range and higher than setpoint value can also be typed into The "FCR
Setpoint =" field which updates the “% increase” field also. The FCR setpoint changes to this value when
the adjacent button is clicked. When clicked, the Increment button changes from gray to red to indicate
that the FCR setpoint has increased to the value in the "FCR Setpoint =" field.
Field Current Step Response - Decrement of FCR Setpoint (A). These two fields indicate the change that
will occur to the FCR setpoint when the corresponding Decrement button is clicked. The "% decrease"
field is used to set and indicate the percentage that the FCR setpoint is decreased when the decrement
button is clicked. The "FCR Setpoint =" indicates the value of current that corresponds to the "%
decrease" field. Any setpoint value within range and lower than setpoint value can also be typed into The
"FCR Setpoint =" field which updates the “% decrease” field also. The FCR setpoint changes to this value
when the adjacent button is clicked. When clicked, the Decrement button changes from gray to red to
indicate that the FCR setpoint has decreased to the value in the "FCR Setpoint =" field.
Field Current Step Response - Meter. The meter in the FCR tab shows the value selected. If an FCR
setpoint value is sent by increase, decrease or setpoint button the meter shows the corresponding value
and meter value text box also displays it. Any value within the range can either be input to meter value
text box or selected by dragging the pointer in the meter, using mouse. This value can then be sent to the
unit by pressing Send button.
The setpoint value currently set in the unit by any of the above methods is displayed in the current
setpoint textbox. To return to the nominal setting the button adjacent to FCR Setpoint (I) (Nominal) should
be pressed. If the FCR Analysis screen is left without returning to nominal setpoint a message box is
shown (Figure 28) which allows the user to return to nominal setpoint by pressing YES or remain at the
current setpoint by pressing NO.