beautypg.com

Basler Electric BE2000E User Manual

Page 15

background image

9287500995 Rev B

7

Single-phase/Three-phase select – LED #2 Blinking Slowly

LED

MODE

5

N/A

4

N/A

3

Three-phase

2

N/A

1

Single-phase

Table 6. Manual Mode (On/Off) Select

Manual Mode On/Off – LED #3 Blinking Slowly

LED

MODE

12

N/A

11

N/A

10

N/A

9

N/A

8

N/A

7

N/A

6

N/A

5

N/A

4

N/A

3

N/A

2

ON

1

OFF

Table 7. Manual Mode (If – Limit) Adjustment Ranges

Manual Mode Adjust – LED #4 Blinking Slowly

Adjustment Range: 0 to 3 Adc

Increment: 0.01 Adc

LED

Minimum Value

Maximum Value

12

2.75

3

11

2.50

2.74

10

2.25

2.49

9

2.00

2.24

8

1.75

1.99

7

1.50

1.74

6

1.25

1.49

5

1.00

1.24

4

0.75

0.99

3

0.50

0.74

2

0.25

0.49

1

0

0.24

BE2000E