Basler Electric BE2000E User Manual
Page 52

44
9287500995 Rev B
Figure 25. Analysis Screen, AVR Tab
The setpoint value currently set in the unit by any of the above methods is displayed in the current
setpoint textbox. To return to the nominal setting, the button adjacent to AVR Setpoint (V) (Nominal)
should be pressed. If the AVR Analysis screen is left without returning to nominal setpoint, a message
box (Figure 26) is shown which allows the user to return to nominal setpoint by pressing YES or remain at
the current setpoint by pressing NO.
Figure 26. Message Box - Return to AVR Nominal Setpoint
FCR Tab
Figure 27 illustrates the settings, sensing values, and alarm signal indicators of the FCR tab. The settings
of the FCR tab make it possible to increment and decrement the FCR setpoint of the BE2000E. The
sensing values and alarm signal indicators of the FCR tab are also displayed by the other tabs of the
Analysis screen.
Field Current Step Response - FCR Setpoint (A). This read-only field indicates the FCR setpoint. (The
FCR setpoint is set by using the Setpoint tab of the Setting Adjustments screen). The current displayed in
the FCR Setpoint field is selected by clicking the adjacent pushbutton. Clicking this button sends the FCR
Setpoint value to the BE2000E and changes the color of the pushbutton from gray to red.
BESTCOMS
™ Software
BE2000E