Basler Electric BE1-11 Modbus Protocol User Manual
Page 98

92
9424200774 Rev B
Register Table
BE1-11
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
51-6
Constant B
SG0
22086
4770*
Float
4
R W
n/a
0 - 25
FGIT
51-6
Constant C
SG0
22088
4772*
Float
4
R W
n/a
0 - 1
FGIT
51-6
Constant N
SG0
22090
4774*
Float
4
R W
n/a
0.5 - 2.5
FGIT
51-6
Constant R
SG0
22092
4776*
Float
4
R W
n/a
0 - 30
FGIT
51-6
Voltage
Restraint
Setpoint
SG0
22094
4778*
Float
4
R W
Volt
30 - 250
FGIT
51-6
Voltage
Restraint
Mode
SG0
22096
4780*
Uint32
4
R W
n/a
Disabled=0
Control=1
Restraint=2
FGIT
51-6
Mode
SG1
22098
4782*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIT
51-6
Source
SG1
22100
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIT
51-6
Pickup
SG1
22102
4784*
Float
4
R W
Amp
0.5 - 16
FGIT
51-6
Curve Index
SG1
22104
4786*
Uint32
4
R W
n/a
S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13,
C=14, G=15, F=16,
46=17, P=18, T1=19,
T2=20, T3=21, T4=22,
A1=23, B1=24, C1=25,
D1=26, E3=27, F1=28
FGIT
51-6
Direction
SG1
22106
4788*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
51-6
Use
Instantaneous
Reset
SG1
22108
4790*
Uint32
4
R W
n/a
Integrating=0
Instantaneous=1
FGIT
51-6
Constant TD
SG1
22110
4792*
Float
4
R W
n/a
0 - 9.9
FGIT
51-6
Constant A
SG1
22112
4794*
Float
4
R W
n/a
0 - 600
FGIT
51-6
Constant B
SG1
22114
4796*
Float
4
R W
n/a
0 - 25
FGIT
51-6
Constant C
SG1
22116
4798*
Float
4
R W
n/a
0 - 1
FGIT
51-6
Constant N
SG1
22118
4800*
Float
4
R W
n/a
0.5 - 2.5
FGIT
51-6
Constant R
SG1
22120
4802*
Float
4
R W
n/a
0 - 30
FGIT
51-6
Voltage
Restraint
Setpoint
SG1
22122
4804*
Float
4
R W
Volt
30 - 250
FGIT
51-6
Voltage
Restraint
Mode
SG1
22124
4806*
Uint32
4
R W
n/a
Disabled=0
Control=1
Restraint=2
FGIT
51-6
Mode
SG2
22126
4808*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIT
51-6
Source
SG2
22128
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIT
51-6
Pickup
SG2
22130
4810*
Float
4
R W
Amp
0.5 - 16
FGIT