148
9424200774 Rev B
Register Table
BE1-11
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
49RTD-9
Mode
SG1
25608
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT
49RTD-9
Source
SG1
25610
Uint32
4
R W
n/a
Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6
FGIMT
49RTD-9
Over Pickup
SG1
25612
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-9
Under Pickup
SG1
25614
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-9
Time Delay
SG1
25616
Float
4
R W
Millisecond 0 - 600000
FGIMT
49RTD-9
Voting
SG1
25618
Uint32
4
R W
n/a
1 - 24
FGIMT
49RTD-9
Mode
SG2
25620
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT
49RTD-9
Source
SG2
25622
Uint32
4
R W
n/a
Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6
FGIMT
49RTD-9
Over Pickup
SG2
25624
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-9
Under Pickup
SG2
25626
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-9
Time Delay
SG2
25628
Float
4
R W
Millisecond 0 - 600000
FGIMT
49RTD-9
Voting
SG2
25630
Uint32
4
R W
n/a
1 - 24
FGIMT
49RTD-9
Mode
SG3
25632
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT
49RTD-9
Source
SG3
25634
Uint32
4
R W
n/a
Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6
FGIMT
49RTD-9
Over Pickup
SG3
25636
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-9
Under Pickup
SG3
25638
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-9
Time Delay
SG3
25640
Float
4
R W
Millisecond 0 - 600000
FGIMT
49RTD-9
Voting
SG3
25642
Uint32
4
R W
n/a
1 - 24
FGIMT
49RTD-10
Mode
SG0
25644
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT
49RTD-10
Source
SG0
25646
Uint32
4
R W
n/a
Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6
FGIMT
49RTD-10
Over Pickup
SG0
25648
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-10
Under Pickup
SG0
25650
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-10
Time Delay
SG0
25652
Float
4
R W
Millisecond 0 - 600000
FGIMT
49RTD-10
Voting
SG0
25654
Uint32
4
R W
n/a
1 - 24
FGIMT
49RTD-10
Mode
SG1
25656
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT
49RTD-10
Source
SG1
25658
Uint32
4
R W
n/a
Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6
FGIMT
49RTD-10
Over Pickup
SG1
25660
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-10
Under Pickup
SG1
25662
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-10
Time Delay
SG1
25664
Float
4
R W
Millisecond 0 - 600000
FGIMT
49RTD-10
Voting
SG1
25666
Uint32
4
R W
n/a
1 - 24
FGIMT
49RTD-10
Mode
SG2
25668
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT