Basler Electric BE1-11 Modbus Protocol User Manual
Page 79

9424200774 Rev B
73
BE1-11
Register Table
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
59X-4
Time Multiplier
SG3
21236
4018*
Float
4
R W
n/a
0 - 9.9
FGIT
67
Mode
SG0
21238
4020*
Uint32
4
R W
n/a
Disabled=0
Enabled=1
FGIT
Reserved
21240-
41
67
Zero
Sequence
Mode
SG0
21242
4022*
Uint32
4
R W
n/a
VOIN=0
VOIG=1
VXIN=2
VXIG=3
FGIT
67
QVI Mode
SG0
21244
4024*
Uint32
4
R W
n/a
I=1
V=2
VI=3
Q=4
QI=5
QV=6
QVI=7
FGIT
67
Mode
SG1
21246
4026*
Uint32
4
R W
n/a
Disabled=0
Enabled=1
FGIT
Reserved
21248-
49
67
Zero
Sequence
Mode
SG1
21250
4028*
Uint32
4
R W
n/a
VOIN=0
VOIG=1
VXIN=2
VXIG=3
FGIT
67
QVI Mode
SG1
21252
4030*
Uint32
4
R W
n/a
I=1
V=2
VI=3
Q=4
QI=5
QV=6
QVI=7
FGIT
67
Mode
SG2
21254
4032*
Uint32
4
R W
n/a
Disabled=0
Enabled=1
FGIT
Reserved
21256-
57
67
Zero
Sequence
Mode
SG2
21258
4034*
Uint32
4
R W
n/a
VOIN=0
VOIG=1
VXIN=2
VXIG=3
FGIT
67
QVI Mode
SG2
21260
4036*
Uint32
4
R W
n/a
I=1
V=2
VI=3
Q=4
QI=5
QV=6
QVI=7
FGIT
67
Mode
SG3
21262
4038*
Uint32
4
R W
n/a
Disabled=0
Enabled=1
FGIT
Reserved
21264-
65
67
Zero
Sequence
Mode
SG3
21266
4040*
Uint32
4
R W
n/a
VOIN=0
VOIG=1
VXIN=2
VXIG=3
FGIT
67
QVI Mode
SG3
21268
4042*
Uint32
4
R W
n/a
I=1
V=2
VI=3
Q=4
QI=5
QV=6
QVI=7
FGIT
50-1
Mode
SG0
21270
4044*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
FGIMT
50-1
Source
SG0
21272
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-1
Pickup
SG0
21274
4046*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-1
Time Delay
SG0
21276
4048*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-1
Direction
SG0
21278
4050*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT