Basler Electric BE1-11 Modbus Protocol User Manual
Page 101

9424200774 Rev B
95
BE1-11
Register Table
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
51-7
Constant B
SG1
22226
4900*
Float
4
R W
n/a
0 - 25
FGIT
51-7
Constant C
SG1
22228
4902*
Float
4
R W
n/a
0 - 1
FGIT
51-7
Constant N
SG1
22230
4904*
Float
4
R W
n/a
0.5 - 2.5
FGIT
51-7
Constant R
SG1
22232
4906*
Float
4
R W
n/a
0 - 30
FGIT
51-7
Voltage
Restraint
Setpoint
SG1
22234
4908*
Float
4
R W
Volt
30 - 250
FGIT
51-7
Voltage
Restraint
Mode
SG1
22236
4910*
Uint32
4
R W
n/a
Disabled=0
Control=1
Restraint=2
FGIT
51-7
Mode
SG2
22238
4912*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIT
51-7
Source
SG2
22240
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIT
51-7
Pickup
SG2
22242
4914*
Float
4
R W
Amp
0.5 - 16
FGIT
51-7
Curve Index
SG2
22244
4916*
Uint32
4
R W
n/a
S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13,
C=14, G=15, F=16,
46=17, P=18, T1=19,
T2=20, T3=21, T4=22,
A1=23, B1=24, C1=25,
D1=26, E3=27, F1=28
FGIT
51-7
Direction
SG2
22246
4918*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
51-7
Use
Instantaneous
Reset
SG2
22248
4920*
Uint32
4
R W
n/a
Integrating=0
Instantaneous=1
FGIT
51-7
Constant TD
SG2
22250
4922*
Float
4
R W
n/a
0 - 9.9
FGIT
51-7
Constant A
SG2
22252
4924*
Float
4
R W
n/a
0 - 600
FGIT
51-7
Constant B
SG2
22254
4926*
Float
4
R W
n/a
0 - 25
FGIT
51-7
Constant C
SG2
22256
4928*
Float
4
R W
n/a
0 - 1
FGIT
51-7
Constant N
SG2
22258
4930*
Float
4
R W
n/a
0.5 - 2.5
FGIT
51-7
Constant R
SG2
22260
4932*
Float
4
R W
n/a
0 - 30
FGIT
51-7
Voltage
Restraint
Setpoint
SG2
22262
4934*
Float
4
R W
Volt
30 - 250
FGIT
51-7
Voltage
Restraint
Mode
SG2
22264
4936*
Uint32
4
R W
n/a
Disabled=0
Control=1
Restraint=2
FGIT
51-7
Mode
SG3
22266
4938*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIT
51-7
Source
SG3
22268
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIT
51-7
Pickup
SG3
22270
4940*
Float
4
R W
Amp
0.5 - 16
FGIT