Register table, Conventions, General – Basler Electric BE1-11 Modbus Protocol User Manual
Page 19

9424200774 Rev B
13
BE1-11
Register Table
Register Table
Parameters are mapped into the holding register address space in blocks according to access type.
Registers 9875 through 9999 are reserved for user configurable polling block, and register 9874 is
reserved for system use only. By default, all registers in the polling block are mapped to register 9874
when their value is zero. Use BESTCOMSPlus
® to map desired data to poll block registers to be read by
one Modbus
™ read request.
Any holding register not listed in the register table is an unassigned holding register. Reading or writing to
unassigned holding registers is not allowed and error code “Illegal Data Address” will be reported.
Reading/Writing any data (variable) as its complete (atomic) value is the only legal operation. Partially
requested data will return an error. For example, request for reading/writing of/to only register 620 will
return an error because this register is part of data Settings Group-Direct Operate that is mapped to 2
registers. Reading of register 620 is correct only if reading/writing of both 620 and 621 are requested in
the same query.
Conventions
The Type column uses the following abbreviations:
•
String - ASCII string
•
Float - Floating point
•
Int32 - Integer (32-bit integer)
•
Int16 - Integer (16-bit integer)
•
Int8 - Integer (8-bit integer)
•
Uint32 - Unsigned Integer (32-bit integer)
•
Uint16 - Unsigned Integer (16-bit integer)
•
Uint8 - Unsigned Integer (8-bit integer)
•
IP Address - IP Address
The Style column uses the following abbreviations:
•
F - Feeder Protection System
•
G - Generator Protection System
•
I - Intertie Protection System
•
M - Motor Protection System
•
T - Transformer Protection System
Register Table
The register table on the following pages contains the following groups:
General, SBO Select, SBO Operate, Direct Operate, Binary Points, Reporting, Power Quality, Fault
Record, Relay Settings, Reporting Setup, Power Quality Setup, Demand Setup, Fault Record Setup, Poll
Block Settings, Metering, Demand Data, Global Settings, Protection Settings, and User Labels.
General
Name
Description
Register
Type
Bytes
Writable
Range
System Data
Default Graphics Module Version
1
String
13
R
0 - 13
System Data
Alternate Graphics Module Version
8
String
13
R
0 - 13
System Data
Model Number
15
String
64
R
0 - 64
Reserved
47-110
System Data
Boot Version Information
111
String
64
R
0 - 64
Reserved
143-206
System Data
Firmware Part Number
207
String
64
R
0 - 64
Unit Info
Style Number
239
String
32
R
0 - 32
Unit Info
Model Number
255
String
64
R
0 - 64
Unit Info
App Part Number
287
String
64
R
0 - 64
Unit Info
Serial Number
319
String
32
R
0 - 32