Basler Electric BE1-11 Modbus Protocol User Manual
Page 55

9424200774 Rev B
49
BE1-11
Register Table
Name
Description
Register
Type
Bytes Writable
Unit
Range
Style
Analog Input
Config 4
Type
18374
Uint32 4
R W
n/a
Voltage=0
Current=1
FGIMT
Analog Input
Config 4
Parameter
Minimum
18376
Float
4
R W
n/a
-199999.8
FGIMT
Analog Input
Config 4
Parameter
Maximum
18378
Float
4
R W
n/a
-199999.8
FGIMT
Analog Input
Config 4
Input Current
Minimum
18380
Float
4
R W
Milliamp
4 - 20
FGIMT
Analog Input
Config 4
Input Current
Maximum
18382
Float
4
R W
Milliamp
4 - 20
FGIMT
Analog Input
Config 4
Input Voltage
Minimum
18384
Float
4
R W
Volt
0 - 10
FGIMT
Analog Input
Config 4
Input Voltage
Maximum
18386
Float
4
R W
Volt
0 - 10
FGIMT
Analog Output
Config 1
Type
18388
Uint32 4
R W
n/a
Voltage=0
Current=1
FGIMT
Analog Output
Config 1
Parameter
Minimum
18390
Float
4
R W
n/a
-199999.8
FGIMT
Analog Output
Config 1
Parameter
Maximum
18392
Float
4
R W
n/a
-199999.8
FGIMT
Analog Output
Config 1
Output
Current
Minimum
18394
Float
4
R W
Milliamp
4 - 20
FGIMT
Analog Output
Config 1
Output
Current
Maximum
18396
Float
4
R W
Milliamp
4 - 20
FGIMT
Analog Output
Config 1
Output
Voltage
Minimum
18398
Float
4
R W
Volt
0 - 10
FGIMT
Analog Output
Config 1
Output
Voltage
Maximum
18400
Float
4
R W
Volt
0 - 10
FGIMT
Analog Output
Config 1
Parameter
Selection
18402
Uint32 4
R W
n/a
VA=0, VB=1, VC=2, VAB=3, VBC=4, VCA=5,
3V0=6, V1=7, V2=8, IA-1=9, IB-1=10, IC-1=11, 3I0-
1=12, I1-1=13, I2-1=14, IG-1=15, IA-2=16, IB-2=17,
IC-2=18, 3I0-2=19, I1-2=20, I2-2=21, IG-2=22,
Analog Input 1=21, Phase Frequency=23, Aux
Frequency=24, Power Factor=25, Real Power=26,
Imaginary Power=27, Apparent Power=28, Analog
Input 1-1=29, Analog Input 1-2=30, Analog Input 1-
3=31, Analog Input 1-4=32, Analog Input 2-1=33,
Analog Input 2-2=34, Analog Input 2-3=35, Analog
Input 2-4=36, RTD 1-1=37 RTD 1-2=38, RTD 1-
3=39, RTD 1-4=40, RTD 1-5=41, RTD 1-6=42, RTD
1-7=43, RTD 1-8=44, RTD 1-9=45, RTD 1-10=46,
RTD 1-11=47, RTD 1-12=48, RTD 2-1=49, RTD 2-
2=50, RTD 2-3=51, RTD 2-4=52, RTD 2-5=53, RTD
2-6=54, RTD 2-7-55, RTD 2-8=56, RTD 2-9=57,
RTD 2-10=58, RTD 2-11=59, RTD 2-12=60
FGIMT
Analog Output
Config 2
Type
18404
Uint32 4
R W
n/a
Voltage=0
Current=1
FGIMT
Analog Output
Config 2
Param
Minimum
18406
Float
4
R W
n/a
-199999.8
FGIMT
Analog Output
Config 2
Parameter
Maximum
18408
Float
4
R W
n/a
-199999.8
FGIMT
Analog Output
Config 2
Output
Current
Minimum
18410
Float
4
R W
Milliamp
4 - 20
FGIMT
Analog Output
Config 2
Output
Current
Maximum
18412
Float
4
R W
Milliamp
4 - 20
FGIMT
Analog Output
Config 2
Output
Voltage
Minimum
18414
Float
4
R W
Volt
0 - 10
FGIMT
Analog Output
Config 2
Output
Voltage
Maximum
18416
Float
4
R W
Volt
0 - 10
FGIMT