Basler Electric BE1-11 Modbus Protocol User Manual
Page 136

130
9424200774 Rev B
Register Table
BE1-11
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
87
Source
SG1
24324
Uint32
4
R W
n/a
CT1=0
CT2=1
GMT
87
Min Restrained
Pickup Value
SG1
24326
Float
4
R W
n/a
0.1 - 1
GMT
87
Second
Restrained
Pickup Value
SG1
24328
Float
4
R W
n/a
1 - 20
GMT
87
Restraint
Slope Mode
SG1
24330
Uint32
4
R W
n/a
Maximum=0
Average=1
GMT
87
Restraint
Slope 1
SG1
24332
Float
4
R W
Percent
5 - 100
GMT
87
Restraint
Slope 2
SG1
24334
Float
4
R W
Percent
15 - 140
GMT
87
Alarm Slope
SG1
24336
Float
4
R W
Percent
50 - 100
GMT
Reserved
24338-
39
87
2
nd
Harmonic
Restraint
SG1
24340
Float
4
R W
Percent
0 - 75
GT
87
5
th
Harmonic
SG1
24342
Float
4
R W
Percent
0 - 75
GT
87
Shared
Harmonic
Restraint
SG1
24344
Uint32
4
R W
n/a
Independent=0
Shared=1
GMT
87
Unrestrained
Pickup Mode
SG1
24346
Uint32
4
R W
n/a
Disabled=0
Enabled=1
GMT
87
Unrestrained
Pickup Value
SG1
24348
Float
4
R W
n/a
0 - 21
GMT
87
Flux Balance
Pickup
SG1
24350
Float
4
R W
Amp
0.1 - 5
GMT
87
Flux Balance
Alarm
SG1
24352
Float
4
R W
Amp
0.1 - 5
GMT
87
Mode
SG2
24354
Uint32
4
R W
n/a
Disabled=0
Percent Differential=1
Flux Balance=2
GMT
87
Time Delay
SG2
24356
Float
4
R W
Millisecond 0 - 60000
GMT
87
Source
SG2
24358
Uint32
4
R W
n/a
CT1=0
CT2=1
GMT
87
Min Restrained
Pickup Value
SG2
24360
Float
4
R W
n/a
0.1 - 1
GMT
87
Second
Restrained
Pickup Value
SG2
24362
Float
4
R W
n/a
1 - 20
GMT
87
Restraint
Slope Mode
SG2
24364
Uint32
4
R W
n/a
Maximum=0
Average=1
GMT
87
Restraint
Slope 1
SG2
24366
Float
4
R W
Percent
5 - 100
GMT
87
Restraint
Slope 2
SG2
24368
Float
4
R W
Percent
15 - 140
GMT
87
Alarm Slope
SG2
24370
Float
4
R W
Percent
50 - 100
GMT
Reserved
24372-
73
87
2
nd
Harmonic
Restraint
SG2
24374
Float
4
R W
Percent
0 - 75
GT
87
5
th
Harmonic
SG2
24376
Float
4
R W
Percent
0 - 75
GT
87
Shared
Harmonic
Restraint
SG2
24378
Uint32
4
R W
n/a
Independent=0
Shared=1
GMT
87
Unrestrained
Pickup Mode
SG2
24380
Uint32
4
R W
n/a
Disabled=0
Enabled=1
GMT
87
Unrestrained
Pickup Value
SG2
24382
Float
4
R W
n/a
0 - 21
GMT
87
Flux Balance
Pickup
SG2
24384
Float
4
R W
Amp
0.1 - 5
GMT
87
Flux Balance
Alarm
SG2
24386
Float
4
R W
Amp
0.1 - 5
GMT
87
Mode
SG3
24388
Uint32
4
R W
n/a
Disabled=0
Percent Differential=1
Flux Balance=2
GMT
87
Time Delay
SG3
24390
Float
4
R W
Millisecond 0 - 60000
GMT
87
Source
SG3
24392
Uint32
4
R W
n/a
CT1=0
CT2=1
GMT
87
Min Restrained
Pickup Value
SG3
24394
Float
4
R W
n/a
0.1 - 1
GMT
87
Second
Restrained
Pickup Value
SG3
24396
Float
4
R W
n/a
1 - 20
GMT
87
Restraint
Slope Mode
SG3
24398
Uint32
4
R W
n/a
Maximum=0
Average=1
GMT
87
Restraint
Slope 1
SG3
24400
Float
4
R W
Percent
5 - 100
GMT