Basler Electric BE1-11 Modbus Protocol User Manual
Page 95

9424200774 Rev B
89
BE1-11
Register Table
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
51-4
Constant B
SG3
21946
4640*
Float
4
R W
n/a
0 - 25
FGIMT
51-4
Constant C
SG3
21948
4642*
Float
4
R W
n/a
0 - 1
FGIMT
51-4
Constant N
SG3
21950
4644*
Float
4
R W
n/a
0.5 - 2.5
FGIMT
51-4
Constant R
SG3
21952
4646*
Float
4
R W
n/a
0 - 30
FGIMT
51-4
Voltage
Restraint
Setpoint
SG3
21954
4648*
Float
4
R W
Volt
30 - 250
FGIMT
51-4
Voltage
Restraint
Mode
SG3
21956
4650*
Uint32
4
R W
n/a
Disabled=0
Control=1
Restraint=2
FGIMT
51-5
Mode
SG0
21958
4652*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
51-5
Source
SG0
21960
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
51-5
Pickup
SG0
21962
4654*
Float
4
R W
Amp
0.5 - 16
FGIMT
51-5
Curve Index
SG0
21964
4656*
Uint32
4
R W
n/a
S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13,
C=14, G=15, F=16,
46=17, P=18, T1=19,
T2=20, T3=21, T4=22,
A1=23, B1=24, C1=25,
D1=26, E3=27, F1=28
FGIMT
51-5
Direction
SG0
21966
4658*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
51-5
Use
Instantaneous
Reset
SG0
21968
4660*
Uint32
4
R W
n/a
Integrating=0
Instantaneous=1
FGIMT
51-5
Constant TD
SG0
21970
4662*
Float
4
R W
n/a
0 - 9.9
FGIMT
51-5
Constant A
SG0
21972
4664*
Float
4
R W
n/a
0 - 600
FGIMT
51-5
Constant B
SG0
21974
4666*
Float
4
R W
n/a
0 - 25
FGIMT
51-5
Constant C
SG0
21976
4668*
Float
4
R W
n/a
0 - 1
FGIMT
51-5
Constant N
SG0
21978
4670*
Float
4
R W
n/a
0.5 - 2.5
FGIMT
51-5
Constant R
SG0
21980
4672*
Float
4
R W
n/a
0 - 30
FGIMT
51-5
Voltage
Restraint
Setpoint
SG0
21982
4674*
Float
4
R W
Volt
30 - 250
FGIMT
51-5
Voltage
Restraint
Mode
SG0
21984
4676*
Uint32
4
R W
n/a
Disabled=0
Control=1
Restraint=2
FGIMT
51-5
Mode
SG1
21986
4678*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
51-5
Source
SG1
21988
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
51-5
Pickup
SG1
21990
4680*
Float
4
R W
Amp
0.5 - 16
FGIMT