Basler Electric BE1-11 Modbus Protocol User Manual
Page 155
9424200774 Rev B
149
BE1-11
Register Table
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
49RTD-10
Source
SG2
25670
Uint32
4
R W
n/a
Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6
FGIMT
49RTD-10
Over Pickup
SG2
25672
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-10
Under Pickup
SG2
25674
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-10
Time Delay
SG2
25676
Float
4
R W
Millisecond 0 - 600000
FGIMT
49RTD-10
Voting
SG2
25678
Uint32
4
R W
n/a
1 - 24
FGIMT
49RTD-10
Mode
SG3
25680
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT
49RTD-10
Source
SG3
25682
Uint32
4
R W
n/a
Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6
FGIMT
49RTD-10
Over Pickup
SG3
25684
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-10
Under Pickup
SG3
25686
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-10
Time Delay
SG3
25688
Float
4
R W
Millisecond 0 - 600000
FGIMT
49RTD-10
Voting
SG3
25690
Uint32
4
R W
n/a
1 - 24
FGIMT
49RTD-11
Mode
SG0
25692
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT
49RTD-11
Source
SG0
25694
Uint32
4
R W
n/a
Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6
FGIMT
49RTD-11
Over Pickup
SG0
25696
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-11
Under Pickup
SG0
25698
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-11
Time Delay
SG0
25700
Float
4
R W
Millisecond 0 - 600000
FGIMT
49RTD-11
Voting
SG0
25702
Uint32
4
R W
n/a
1 - 24
FGIMT
49RTD-11
Mode
SG1
25704
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT
49RTD-11
Source
SG1
25706
Uint32
4
R W
n/a
Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6
FGIMT
49RTD-11
Over Pickup
SG1
25708
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-11
Under Pickup
SG1
25710
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-11
Time Delay
SG1
25712
Float
4
R W
Millisecond 0 - 600000
FGIMT
49RTD-11
Voting
SG1
25714
Uint32
4
R W
n/a
1 - 24
FGIMT
49RTD-11
Mode
SG2
25716
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT
49RTD-11
Source
SG2
25718
Uint32
4
R W
n/a
Configuration Group 1=0
Configuration Group 2=1
Configuration Group 3=2
Configuration Group 4=3
Configuration Group 5=4
Configuration Group 6=5
Configuration Group 7=6
FGIMT
49RTD-11
Over Pickup
SG2
25720
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-11
Under Pickup
SG2
25722
Float
4
R W
Degrees C
0 - 250
FGIMT
49RTD-11
Time Delay
SG2
25724
Float
4
R W
Millisecond 0 - 600000
FGIMT
49RTD-11
Voting
SG2
25726
Uint32
4
R W
n/a
1 - 24
FGIMT
49RTD-11
Mode
SG3
25728
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Over/Under=3
FGIMT