Basler Electric BE1-11 Modbus Protocol User Manual
Page 57

9424200774 Rev B
51
BE1-11
Register Table
Name
Description
Register
Type
Bytes Writable
Unit
Range
Style
Analog Output
Config 4
Parameter
Selection
18450
Uint32 4
R W
n/a
VA=0, VB=1, VC=2, VAB=3, VBC=4, VCA=5,
3V0=6, V1=7, V2=8, IA-1=9, IB-1=10, IC-1=11, 3I0-
1=12, I1-1=13, I2-1=14, IG-1=15, IA-2=16, IB-2=17,
IC-2=18, 3I0-2=19, I1-2=20, I2-2=21, IG-2=22,
Analog Input 1=21, Phase Frequency=23, Aux
Frequency=24, Power Factor=25, Real Power=26,
Imaginary Power=27, Apparent Power=28, Analog
Input 1-1=29, Analog Input 1-2=30, Analog Input 1-
3=31, Analog Input 1-4=32, Analog Input 2-1=33,
Analog Input 2-2=34, Analog Input 2-3=35, Analog
Input 2-4=36, RTD 1-1=37 RTD 1-2=38, RTD 1-
3=39, RTD 1-4=40, RTD 1-5=41, RTD 1-6=42, RTD
1-7=43, RTD 1-8=44, RTD 1-9=45, RTD 1-10=46,
RTD 1-11=47, RTD 1-12=48, RTD 2-1=49, RTD 2-
2=50, RTD 2-3=51, RTD 2-4=52, RTD 2-5=53, RTD
2-6=54, RTD 2-7-55, RTD 2-8=56, RTD 2-9=57,
RTD 2-10=58, RTD 2-11=59, RTD 2-12=60
FGIMT
Motor
Configuration
Full Load
Amps
18452
Float
4
R W
Amp
1 - 25
M
Motor
Configuration
Service
Factor
18454
Float
4
R W
n/a
1 - 1.4
M
Reserved
18456-
57
M
Motor
Configuration
Motor Start
Detection
18458
Uint32 4
R W
n/a
Current Only=0
Current and Contact=1
Contact Only=2
M
Motor
Configuration
Motor Stop
Detection
18460
Uint32 4
R W
n/a
Current Only=0
Current and Contact=1
Contact Only=2
M
Reserved
18462-
63
M
Motor
Maintenance
Data
Hours
Running
18464
Uint32 4
R W
Hour
0 - 2000000
M
Motor
Maintenance
Data
Minutes
Running
18466
Uint32 4
R W
Minute
0 - 59
M
Motor
Maintenance
Data
Max Duration
Start Min
18468
Uint32 4
R W
n/a
0 - 59
M
Motor
Maintenance
Data
Max Duration
Start
Seconds
18470
Uint32 4
R W
n/a
0 - 59
M
Motor
Maintenance
Data
Total
Successful
Norm Starts
18472
Int32
4
R W
n/a
0 - 500000
M
Motor
Maintenance
Data
Total
Successful
Emergency
Starts
18474
Int32
4
R W
n/a
0 - 500000
M
Motor
Maintenance
Data
Total Fail
Norm Starts
18476
Int32
4
R W
n/a
0 - 500000
M
Motor
Maintenance
Data
Total Fail
Emergency
Starts
18478
Int32
4
R W
n/a
0 - 500000
M
Motor
Maintenance
Data
Total Number
Trips
18480
Int32
4
R W
n/a
0 - 500000
M
Motor
Maintenance
Data
Total Number
Thermal Trips
18482
Int32
4
R W
n/a
0 - 500000
M
Motor
Maintenance
Data
Maximum
Thermal Start
18484
Float
4
R W
Percent
0 - 1000
M
Motor
Maintenance
Data
Maximum Cur
Start
18486
Float
4
R W
Amp
0 - 2000000000
M
Motor
Maintenance
Data
Minimum Volt
Start
18488
Float
4
R W
Volt
0 - 2000000000
M
Motor
Maintenance
Data
Hot RTD
Group 1
18490
Float
4
R W
n/a
0 - 250
M
Motor
Maintenance
Data
Hot RTD
Group 2
18492
Float
4
R W
n/a
0 - 250
M
Motor
Maintenance
Data
Hot RTD
Group 3
18494
Float
4
R W
n/a
0 - 250
M