Register Table
BE1-11
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
50-3
Mode
SG1
21360
4116*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-3
Source
SG1
21362
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-3
Pickup
SG1
21364
4118*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-3
Time Delay
SG1
21366
4120*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-3
Direction
SG1
21368
4122*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-3
Mode
SG2
21370
4124*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-3
Source
SG2
21372
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-3
Pickup
SG2
21374
4126*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-3
Time Delay
SG2
21376
4128*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-3
Direction
SG2
21378
4130*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-3
Mode
SG3
21380
4132*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-3
Source
SG3
21382
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-3
Pickup
SG3
21384
4134*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-3
Time Delay
SG3
21386
4136*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-3
Direction
SG3
21388
4138*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-4
Mode
SG0
21390
4140*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-4
Source
SG0
21392
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-4
Pickup
SG0
21394
4142*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-4
Time Delay
SG0
21396
4144*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-4
Direction
SG0
21398
4146*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT