Basler Electric BE1-11 Modbus Protocol User Manual
Page 112

106
9424200774 Rev B
Register Table
BE1-11
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
81-6
Mode
SG3
22860
5498*
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5
FGIT
81-6
Pickup
SG3
22862
5500*
Float
4
R W
Hertz
15 - 70
FGIT
81-6
Time Delay
SG3
22864
5502*
Float
4
R W
Millisecond 0 - 600000
FGIT
81-6
Voltage Inhibit
SG3
22866
5504*
Float
4
R W
Volt
15 - 250
FGIT
81-6
Negative
Sequence
Inhibit
SG3
22868
5506*
Float
4
R W
Percent
0 - 99
FGIT
81-6
Over
Frequency
SG3
22870
5508*
Float
4
R W
Hertz
15 - 70
FGIT
81-6
Under
Frequency
SG3
22872
5510*
Float
4
R W
Hertz
15 - 70
FGIT
81-7
Mode
SG0
22874
5512*
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5
FGIT
81-7
Pickup
SG0
22876
5514*
Float
4
R W
Hertz
15 - 70
FGIT
81-7
Time Delay
SG0
22878
5516*
Float
4
R W
Millisecond 0 - 600000
FGIT
81-7
Voltage Inhibit
SG0
22880
5518*
Float
4
R W
Volt
15 - 250
FGIT
81-7
Negative
Sequence
Inhibit
SG0
22882
5520*
Float
4
R W
Percent
0 - 99
FGIT
81-7
Over
Frequency
SG0
22884
5522*
Float
4
R W
Hertz
15 - 70
FGIT
81-7
Under
Frequency
SG0
22886
5524*
Float
4
R W
Hertz
15 - 70
FGIT
81-7
Mode
SG1
22888
5526*
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5
FGIT
81-7
Pickup
SG1
22890
5528*
Float
4
R W
Hertz
15 - 70
FGIT
81-7
Time Delay
SG1
22892
5530*
Float
4
R W
Millisecond 0 - 600000
FGIT
81-7
Voltage Inhibit
SG1
22894
5532*
Float
4
R W
Volt
15 - 250
FGIT
81-7
Negative
Sequence
Inhibit
SG1
22896
5534*
Float
4
R W
Percent
0 - 99
FGIT
81-7
Over
Frequency
SG1
22898
5536*
Float
4
R W
Hertz
15 - 70
FGIT
81-7
Under
Frequency
SG1
22900
5538*
Float
4
R W
Hertz
15 - 70
FGIT
81-7
Mode
SG2
22902
5540*
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
Rate of Change=3
Positive Rate of
Change=4
Negative Rate of
Change=5
FGIT
81-7
Pickup
SG2
22904
5542*
Float
4
R W
Hertz
15 - 70
FGIT
81-7
Time Delay
SG2
22906
5544*
Float
4
R W
Millisecond 0 - 600000
FGIT
81-7
Voltage Inhibit
SG2
22908
5546*
Float
4
R W
Volt
15 - 250
FGIT
81-7
Negative
Sequence
Inhibit
SG2
22910
5548*
Float
4
R W
Percent
0 - 99
FGIT