Reporting setup, Power quality setup, Demand setup – Basler Electric BE1-11 Modbus Protocol User Manual
Page 41: Fault record setup, Poll block settings

9424200774 Rev B
35
BE1-11
Register Table
Reporting Setup
Name
Description
Register
Type
Bytes
Writable
Major Alarm
Binary Point Number
2700
Uint32
4
R W
Major Alarm
Binary Point State
2702
Uint32
4
R W
Major Alarm
Reset
2704
Uint32
4
R W
Minor Alarm
Binary Point Number
2706
Uint32
4
R W
Minor Alarm
Binary Point State
2708
Uint32
4
R W
Minor Alarm
Reset
2710
Uint32
4
R W
Targets
Binary Point Number
2712
Uint32
4
R W
Targets
Binary Point State
2714
Uint32
4
R W
Targets
Reset
2716
Uint32
4
R W
Relay Alarms
Binary Point Number
2718
Uint32
4
R W
Relay Alarms
Binary Point State
2720
Uint32
4
R W
Relay Alarms
Reset
2722
Uint32
4
R W
Logic Alarms
Binary Point Number
2724
Uint32
4
R W
Logic Alarms
Binary Point State
2726
Uint32
4
R W
Logic Alarms
Reset
2728
Uint32
4
R W
Power Quality Setup
Name
Description
Register
Type
Bytes
Writable
Unit
Range
Power Quality
Reference Mode
2800
Uint32
4
R W
n/a
Fixed=0
Sliding=1
Power Quality
Dip Ratio
2802
Float
4
R W
Ratio
0.7 - 1
Power Quality
Swell Ratio
2804
Float
4
R W
Ratio
1 - 1.3
Power Quality
Dip Hysteresis
2806
Float
4
R W
Ratio
1 - 1.3
Power Quality
Swell Hysteresis
2808
Float
4
R W
Ratio
0.7 - 1
Power Quality
Harmonic to Read
2810
Float
4
R W
n/a
1 - 15
Demand Setup
Name
Description
Register
Type
Bytes
Writable
Unit
Range
Demand Meter
Period-Phase
2900
Float
4
R W
Minute
1 - 60
Demand Meter
Alarm-Threshold Phase
2902
Float
4
R W
Amp
0.5 - 16
Demand Meter
Period-Neutral
2904
Float
4
R W
Minute
1 - 60
Demand Meter
Alarm-Threshold Neutral
2906
Float
4
R W
Amp
0.5 - 16
Demand Meter
Period-I2
2908
Float
4
R W
Minute
1 - 60
Demand Meter
Alarm-Threshold I2
2910
Float
4
R W
Amp
0.5 - 16
Demand Meter
Alarm-Threshold Watt Positive
2912
Float
4
R W
Watt
0 - 8500
Demand Meter
Alarm-Threshold Watt Negative
2914
Float
4
R W
Watt
0 - 8500
Demand Meter
Alarm-Threshold var Positive
2916
Float
4
R W
var
0 - 8500
Demand Meter
Alarm-Threshold var Negative
2918
Float
4
R W
var
0 - 8500
Demand Meter
Alarm-Threshold S
2920
Float
4
R W
VA
0 - 8500
Current Demand Circuit 2
Period-Phase
2922
Float
4
R W
Minute
1 - 60
Current Demand Circuit 2
Alarm-Threshold Phase
2924
Float
4
R W
Amp
0.5 - 16
Current Demand Circuit 2
Period-Neutral
2926
Float
4
R W
Minute
1 - 60
Current Demand Circuit 2
Alarm-Threshold Neutral
2928
Float
4
R W
Amp
0.5 - 16
Current Demand Circuit 2
Period-I2
2930
Float
4
R W
Minute
1 - 60
Current Demand Circuit 2
Alarm-Threshold I2
2932
Float
4
R W
Amp
0.5 - 16
G Current Demand Circuit 2
Period-Neutral
2934
Float
4
R W
Minute
1 - 60
G Current Demand Circuit 2
Alarm-Threshold Neutral
2936
Float
4
R W
Amp
0.5 - 16
Fault Record Setup
Name
Description
Register
Type
Bytes
Writable
Range
Fault Report Selection
Record-Selection
3000
Int32
4
R W
1 - 255
Fault Report
Reset
3002
Uint32
4
R W
n/a
Poll Block Settings
Name
Description
Register
Type
Bytes
Writable
Range
Modbus
DB key For MB Polling Block Register 1
9676
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 2
9677
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 3
9678
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 4
9679
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 5
9680
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 6
9681
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 7
9682
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 8
9683
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 9
9684
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 10
9685
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 11
9686
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 12
9687
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 13
9688
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 14
9689
Uint16
2
R
1 - 9874
Modbus
DB key For MB Polling Block Register 15
9690
Uint16
2
R
1 - 9874