Basler Electric BE1-11 Modbus Protocol User Manual
Page 76

70
9424200774 Rev B
Register Table
BE1-11
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
59X-1
Time Multiplier
SG0
21026
3868*
Float
4
R W
n/a
0 - 9.9
FGIMT
59X-1
Mode
SG1
21028
3870*
Uint32
4
R W
n/a
Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3rd Harmonic=5
FGIMT
Reserved
21030-
33
59X-1
Timing Mode
SG1
21034
3872*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIMT
59X-1
Pickup
SG1
21036
3874*
Float
4
R W
Volt
1 - 150
FGIMT
59X-1
Time Delay
SG1
21038
3876*
Float
4
R W
Millisecond 50 - 600000
FGIMT
59X-1
Time Multiplier
SG1
21040
3878*
Float
4
R W
n/a
0 - 9.9
FGIMT
59X-1
Mode
SG2
21042
3880*
Uint32
4
R W
n/a
Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3rd Harmonic=5
FGIMT
Reserved
21044-
47
59X-1
Timing Mode
SG2
21048
3882*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIMT
59X-1
Pickup
SG2
21050
3884*
Float
4
R W
Volt
1 - 150
FGIMT
59X-1
Time Delay
SG2
21052
3886*
Float
4
R W
Millisecond 50 - 600000
FGIMT
59X-1
Time Multiplier
SG2
21054
3888*
Float
4
R W
n/a
0 - 9.9
FGIMT
59X-1
Mode
SG3
21056
3890*
Uint32
4
R W
n/a
Disabled=0
3V0=1
V1=2
V2=3 Vx Fundamental=4
Vx 3rd Harmonic=5
FGIMT
Reserved
21058-
61
59X-1
Timing Mode
SG3
21062
3892*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIMT
59X-1
Pickup
SG3
21064
3894*
Float
4
R W
Volt
1 - 150
FGIMT
59X-1
Time Delay
SG3
21066
3896*
Float
4
R W
Millisecond 50 - 600000
FGIMT
59X-1
Time Multiplier
SG3
21068
3898*
Float
4
R W
n/a
0 - 9.9
FGIMT
59X-2
Mode
SG0
21070
3900*
Uint32
4
R W
n/a
Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3rd Harmonic=5
FGIMT
Reserved
21072-
75
59X-2
Timing Mode
SG0
21076
3902*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIMT
59X-2
Pickup
SG0
21078
3904*
Float
4
R W
Volt
1 - 150
FGIMT
59X-2
Time Delay
SG0
21080
3906*
Float
4
R W
Millisecond 50 - 600000
FGIMT
59X-2
Time Multiplier
SG0
21082
3908*
Float
4
R W
n/a
0 - 9.9
FGIMT
59X-2
Mode
SG1
21084
3910*
Uint32
4
R W
n/a
Disabled=0
3V0=1
V1=2
V2=3
Vx Fundamental=4
Vx 3rd Harmonic=5
FGIMT
Reserved
21086-
89
59X-2
Timing Mode
SG1
21090
3912*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIMT
59X-2
Pickup
SG1
21092
3914*
Float
4
R W
Volt
1 - 150
FGIMT
59X-2
Time Delay
SG1
21094
3916*
Float
4
R W
Millisecond 50 - 600000
FGIMT