Basler Electric BE1-11 Modbus Protocol User Manual
Page 83

9424200774 Rev B
77
BE1-11
Register Table
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
50-4
Mode
SG1
21400
4148*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-4
Source
SG1
21402
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-4
Pickup
SG1
21404
4150*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-4
Time Delay
SG1
21406
4152*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-4
Direction
SG1
21408
4154*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-4
Mode
SG2
21410
4156*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-4
Source
SG2
21412
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-4
Pickup
SG2
21414
4158*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-4
Time Delay
SG2
21416
4160*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-4
Direction
SG2
21418
4162*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-4
Mode
SG3
21420
4164*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-4
Source
SG3
21422
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-4
Pickup
SG3
21424
4166*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-4
Time Delay
SG3
21426
4168*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-4
Direction
SG3
21428
4170*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-5
Mode
SG0
21430
4172*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-5
Source
SG0
21432
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-5
Pickup
SG0
21434
4174*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-5
Time Delay
SG0
21436
4176*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-5
Direction
SG0
21438
4178*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT