Basler Electric BE1-11 Modbus Protocol User Manual
Page 141

9424200774 Rev B
135
BE1-11
Register Table
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
50-9
Time Delay
SG0
24642
Float
4
R W
Millisecond 0 - 60000
T
50-9
Direction
SG0
24644
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
T
50-9
Mode
SG1
24646
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
T
50-9
Source
SG1
24648
Uint32
4
R W
n/a
CT1=0
CT2=1
T
50-9
Pickup
SG1
24650
Float
4
R W
Amp
0.5 - 150
T
50-9
Time Delay
SG1
24652
Float
4
R W
Millisecond 0 - 60000
T
50-9
Direction
SG1
24654
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
T
50-9
Mode
SG2
24656
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
T
50-9
Source
SG2
24658
Uint32
4
R W
n/a
CT1=0
CT2=1
T
50-9
Pickup
SG2
24660
Float
4
R W
Amp
0.5 - 150
T
50-9
Time Delay
SG2
24662
Float
4
R W
Millisecond 0 - 60000
T
50-9
Direction
SG2
24664
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
T
50-9
Mode
SG3
24666
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
T
50-9
Source
SG3
24668
Uint32
4
R W
n/a
CT1=0
CT2=1
T
50-9
Pickup
SG3
24670
Float
4
R W
Amp
0.5 - 150
T
50-9
Time Delay
SG3
24672
Float
4
R W
Millisecond 0 - 60000
T
50-9
Direction
SG3
24674
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
T
51-8
Mode
SG0
24676
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
T
51-8
Source
SG0
24678
Uint32
4
R W
n/a
CT1=0
CT2=1
T
51-8
Pickup
SG0
24680
Float
4
R W
Amp
0.5 - 16
T
51-8
Curve Index
SG0
24682
Uint32
4
R W
n/a
S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13,
C=14, G=15, F=16,
46=17, P=18, T1=19,
T2=20, T3=21, T4=22,
A1=23, B1=24, C1=25,
D1=26, E3=27, F1=28
T
51-8
Direction
SG0
24684
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
T