Basler Electric BE1-11 Modbus Protocol User Manual
Page 80

74
9424200774 Rev B
Register Table
BE1-11
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
50-1
Mode
SG1
21280
4052*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
FGIMT
50-1
Source
SG1
21282
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-1
Pickup
SG1
21284
4054*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-1
Time Delay
SG1
21286
4056*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-1
Direction
SG1
21288
4058*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-1
Mode
SG2
21290
4060*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-1
Source
SG2
21292
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-1
Pickup
SG2
21294
4062*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-1
Time Delay
SG2
21296
4064*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-1
Direction
SG2
21298
4066*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-1
Mode
SG3
21300
4068*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-1
Source
SG3
21302
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-1
Pickup
SG3
21304
4070*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-1
Time Delay
SG3
21306
4072*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-1
Direction
SG3
21308
4074*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-2
Mode
SG0
21310
4076*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-2
Source
SG0
21312
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-2
Pickup
SG0
21314
4078*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-2
Time Delay
SG0
21316
4080*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-2
Direction
SG0
21318
4082*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT