Basler Electric BE1-11 Modbus Protocol User Manual
Page 28

22
9424200774 Rev B
Register Table
BE1-11
Name
Description
Register
Type
Bytes Writable
Range
Style
79
Shot 2
932 bit 6
Uint16 2
R
True=1 False=0
FI
79
Shot 3
932 bit 7
Uint16 2
R
True=1 False=0
FI
79
Shot 4
932 bit 8
Uint16 2
R
True=1 False=0
FI
79
Reclose Initiate
932 bit 9
Uint16 2
R
True=1 False=0
FI
79
Wait
932 bit 10
Uint16 2
R
True=1 False=0
FI
79
Drive to Lockout
932 bit 11
Uint16 2
R
True=1 False=0
FI
79
Zone Pick Up
932 bit 12
Uint16 2
R
True=1 False=0
FI
79
Zone Trip
932 bit 13
Uint16 2
R
True=1 False=0
FI
50BF
Block
932 bit 14
Uint16 2
R
True=1 False=0
FGIMT
50BF
BFI52
932 bit 15
Uint16 2
R
True=1 False=0
FGIMT
50BF
BFI50
933 bit 0
Uint16 2
R
True=1 False=0
FGIMT
50BF
BFRT
933 bit 1
Uint16 2
R
True=1 False=0
FGIMT
50BF
BFT
933 bit 2
Uint16 2
R
True=1 False=0
FGIMT
50BF
50BF Target
933 bit 3
Uint16 2
R
True=1 False=0
FGIMT
50BF
BFI Alarm
933 bit 4
Uint16 2
R
True=1 False=0
FGIMT
50BF
Current Detected
933 bit 5
Uint16 2
R
True=1 False=0
FGIMT
52
Status
933 bit 6
Uint16 2
R
True=1 False=0
FGIMT
52
52 Alarm
933 bit 7
Uint16 2
R
True=1 False=0
FGIMT
Breaker Monitor
Breaker Monitor Block
933 bit 8
Uint16 2
R
True=1 False=0
FGIMT
Demand Meter
IG Demand Alarm
933 bit 9
Uint16 2
R
True=1 False=0
FGIMT
Demand Meter
IN Demand Alarm
933 bit 10
Uint16 2
R
True=1 False=0
FGIMT
Demand Meter
IP Demand Alarm
933 bit 11
Uint16 2
R
True=1 False=0
FGIMT
Demand Meter
IQ Demand Alarm
933 bit 12
Uint16 2
R
True=1 False=0
FGIMT
Demand Meter
Var Positive Demand Alarm
933 bit 13
Uint16 2
R
True=1 False=0
FGIMT
Demand Meter
Var Negative Demand Alarm
933 bit 14
Uint16 2
R
True=1 False=0
FGIMT
Demand Meter
Watt Forward Demand Alarm
933 bit 15
Uint16 2
R
True=1 False=0
FGIMT
Demand Meter
Watt Reverse Demand Alarm
934 bit 0
Uint16 2
R
True=1 False=0
FGIMT
Demand Meter
S Demand Alarm
934 bit 1
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact Input 1 State
934 bit 2
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact Input 2 State
934 bit 3
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact Input 3 State
934 bit 4
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact Input 4 State
934 bit 5
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact 52 TCM
934 bit 6
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact Output 1 State
934 bit 7
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact Output 2 State
934 bit 8
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact Output 3 State
934 bit 9
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact Output 4 State
934 bit 10
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact Output 5 State
934 bit 11
Uint16 2
R
True=1 False=0
FGIMT
Local Contacts
Contact Output A State
934 bit 12
Uint16 2
R
True=1 False=0
FGIMT
System Data
RF Trigger
934 bit 13
Uint16 2
R
True=1 False=0
FGIMT
System Data
Pickup Logic
934 bit 14
Uint16 2
R
True=1 False=0
FGIMT
System Data
Trip Logic
934 bit 15
Uint16 2
R
True=1 False=0
FGIMT
System Data
Logic Trigger
935 bit 0
Uint16 2
R
True=1 False=0
FGIMT
System Data
Breaker Status
935 bit 1
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Flash Failure Alarm
935 bit 2
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Micro Failure Alarm
935 bit 3
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Calibration Error Alarm
935 bit 4
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Calibration Defaults Alarm
935 bit 5
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Defaults Loaded Alarm
935 bit 6
Uint16 2
R
True=1 False=0
FGIMT
Alarms
System Overload Alarm
935 bit 7
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Power Supply Alarm
935 bit 8
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Changes Lost Alarm
935 bit 9
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Real-Time Clock Alarm
935 bit 10
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Date/Time Set Alarm
935 bit 11
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Firmware Changed Alarm
935 bit 12
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Frequency Out of Range Alarm
935 bit 13
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Ethernet Link Lost Alarm
935 bit 14
Uint16 2
R
True=1 False=0
FGIMT
Reserved
935 bit 15
Alarms
IRIG Sync Lost Alarm
936 bit 0
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Logic = None Alarm
936 bit 1
Uint16 2
R
True=1 False=0
FGIMT
Alarms
No User Setting Alarm
936 bit 2
Uint16 2
R
True=1 False=0
FGIMT
Alarms
NTP Sync Lost Alarm
936 bit 3
Uint16 2
R
True=1 False=0
FGIMT
Alarms
DNP Polls Error
936 bit 4
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Setting Change Alarm
936 bit 5
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Output Override Alarm
936 bit 6
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Analog Alarm
936 bit 7
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Microprocessor Reset Alarm
936 bit 8
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Breaker Monitor 1
936 bit 9
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Breaker Monitor 2
936 bit 10
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Breaker Monitor 3
936 bit 11
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Fault Report Timeout
936 bit 12
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Programmable Alarm 1
936 bit 13
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Programmable Alarm 2
936 bit 14
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Programmable Alarm 3
936 bit 15
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Programmable Alarm 4
937 bit 0
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Programmable Alarm 5
937 bit 1
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Programmable Alarm 6
937 bit 2
Uint16 2
R
True=1 False=0
FGIMT
Alarms
Programmable Alarm 7
937 bit 3
Uint16 2
R
True=1 False=0
FGIMT