Alarms and targets reporting – Basler Electric BE1-11 Modbus Protocol User Manual
Page 161

9424200774 Rev B
155
Alarms and Targets Reporting
Alarm and target information is obtained by reading the appropriate register. If an alarm or target is
present, the register will return numeric a value. In a case where more than one alarm or target is present,
you must repeat reading of the register until a value of zero (0) is returned.
Table 5 lists the reporting registers. Table 6 provides a list of possible alarms and targets reported by
these registers.
Table 5. Reporting Registers
Name
Description
Register
Type
Bytes
Major Alarm
Read Alarms
1206
Uint32
4
Minor Alarm
Read Alarms
1208
Uint32
4
Targets
Read Targets
1210
Uint32
4
Relay Alarms
Read Alarms
1212
Uint32
4
Logic Alarms
Read Alarms
1214
Uint32
4
Table 6. Alarms and Targets
Index
Description
64
60FL Alarm
69
60FL Target
99
24 Target
100
24 Alarm
163
27-1 Target A
164
27-1 Target B
165
27-1 Target C
195
27-2 Target A
196
27-2 Target B
197
27-2 Target C
227
27-3 Target A
228
27-3 Target B
229
27-3 Target C
259
27-4 Target A
260
27-4 Target B
261
27-4 Target C
291
27-5 Target A
292
27-5 Target B
293
27-5 Target C
323
27X-1 Target 3V0
324
27X-1 Target V2
325
27X-1 Target Aux
326
27X-1 Target Vx 3rd Harmonic
327
27X-1 Target V1
355
27X-2 Target 3V0
356
27X-2 Target V2
357
27X-2 Target Aux
358
27X-2 Target Vx 3rd Harmonic
BE1-11
Alarms and Targets Reporting