Basler Electric BE1-11 Modbus Protocol User Manual
Page 26

20
9424200774 Rev B
Register Table
BE1-11
Name
Description
Register
Type
Bytes Writable
Range
Style
40Q
Pickup
922 bit 10
Uint16 2
R
True=1 False=0
GM
40Q
Trip
922 bit 11
Uint16 2
R
True=1 False=0
GM
40Q
Target
922 bit 12
Uint16 2
R
True=1 False=0
GM
81-1
Block
922 bit 13
Uint16 2
R
True=1 False=0
FGIMT
81-1
Pickup
922 bit 14
Uint16 2
R
True=1 False=0
FGIMT
81-1
Trip
922 bit 15
Uint16 2
R
True=1 False=0
FGIMT
81-1
Target Over
923 bit 0
Uint16 2
R
True=1 False=0
FGIMT
81-1
Target Under
923 bit 1
Uint16 2
R
True=1 False=0
FGIMT
81-1
Target Rate of Change
923 bit 2
Uint16 2
R
True=1 False=0
FGIMT
81-2
Block
923 bit 3
Uint16 2
R
True=1 False=0
FGIMT
81-2
Pickup
923 bit 4
Uint16 2
R
True=1 False=0
FGIMT
81-2
Trip
923 bit 5
Uint16 2
R
True=1 False=0
FGIMT
81-2
Target Over
923 bit 6
Uint16 2
R
True=1 False=0
FGIMT
81-2
Target Under
923 bit 7
Uint16 2
R
True=1 False=0
FGIMT
81-2
Target Rate of Change
923 bit 8
Uint16 2
R
True=1 False=0
FGIMT
81-3
Block
923 bit 9
Uint16 2
R
True=1 False=0
FGIMT
81-3
Pickup
923 bit 10
Uint16 2
R
True=1 False=0
FGIMT
81-3
Trip
923 bit 11
Uint16 2
R
True=1 False=0
FGIMT
81-3
Target Over
923 bit 12
Uint16 2
R
True=1 False=0
FGIMT
81-3
Target Under
923 bit 13
Uint16 2
R
True=1 False=0
FGIMT
81-3
Target Rate of Change
923 bit 14
Uint16 2
R
True=1 False=0
FGIMT
81-4
Block
923 bit 15
Uint16 2
R
True=1 False=0
FGIMT
81-4
Pickup
924 bit 0
Uint16 2
R
True=1 False=0
FGIMT
81-4
Trip
924 bit 1
Uint16 2
R
True=1 False=0
FGIMT
81-4
Target Over
924 bit 2
Uint16 2
R
True=1 False=0
FGIMT
81-4
Target Under
924 bit 3
Uint16 2
R
True=1 False=0
FGIMT
81-4
Target Rate of Change
924 bit 4
Uint16 2
R
True=1 False=0
FGIMT
81-5
Block
924 bit 5
Uint16 2
R
True=1 False=0
FGIT
81-5
Pickup
924 bit 6
Uint16 2
R
True=1 False=0
FGIT
81-5
Trip
924 bit 7
Uint16 2
R
True=1 False=0
FGIT
81-5
Target Over
924 bit 8
Uint16 2
R
True=1 False=0
FGIT
81-5
Target Under
924 bit 9
Uint16 2
R
True=1 False=0
FGIT
81-5
Target Rate of Change
924 bit 10
Uint16 2
R
True=1 False=0
FGIT
81-6
Block
924 bit 11
Uint16 2
R
True=1 False=0
FGIT
81-6
Pickup
924 bit 12
Uint16 2
R
True=1 False=0
FGIT
81-6
Trip
924 bit 13
Uint16 2
R
True=1 False=0
FGIT
81-6
Target Over
924 bit 14
Uint16 2
R
True=1 False=0
FGIT
81-6
Target Under
924 bit 15
Uint16 2
R
True=1 False=0
FGIT
81-6
Target Rate of Change
925 bit 0
Uint16 2
R
True=1 False=0
FGIT
81-7
Block
925 bit 1
Uint16 2
R
True=1 False=0
FGIT
81-7
Pickup
925 bit 2
Uint16 2
R
True=1 False=0
FGIT
81-7
Trip
925 bit 3
Uint16 2
R
True=1 False=0
FGIT
81-7
Target Over
925 bit 4
Uint16 2
R
True=1 False=0
FGIT
81-7
Target Under
925 bit 5
Uint16 2
R
True=1 False=0
FGIT
81-7
Target Rate of Change
925 bit 6
Uint16 2
R
True=1 False=0
FGIT
81-8
Block
925 bit 7
Uint16 2
R
True=1 False=0
FGIT
81-8
Pickup
925 bit 8
Uint16 2
R
True=1 False=0
FGIT
81-8
Trip
925 bit 9
Uint16 2
R
True=1 False=0
FGIT
81-8
Target Over
925 bit 10
Uint16 2
R
True=1 False=0
FGIT
81-8
Target Under
925 bit 11
Uint16 2
R
True=1 False=0
FGIT
81-8
Target Rate of Change
925 bit 12
Uint16 2
R
True=1 False=0
FGIT
43-1
Pulse
925 bit 13
Uint16 2
R
True=1 False=0
FGIMT
43-1
Reset
925 bit 14
Uint16 2
R
True=1 False=0
FGIMT
43-1
Set
925 bit 15
Uint16 2
R
True=1 False=0
FGIMT
43-1
Output
926 bit 0
Uint16 2
R
True=1 False=0
FGIMT
Reserved
926 bit 1
43-1
Tag Blocking
926 bit 2
Uint16 2
R
True=1 False=0
FGIMT
43-1
Tag Informational
926 bit 3
Uint16 2
R
True=1 False=0
FGIMT
43-1
Untag Blocking
926 bit 4
Uint16 2
R
True=1 False=0
FGIMT
43-1
Untag Informational
926 bit 5
Uint16 2
R
True=1 False=0
FGIMT
43-1
Tag Blocking Status
926 bit 6
Uint16 2
R
True=1 False=0
FGIMT
43-1
Tag Informational Status
926 bit 7
Uint16 2
R
True=1 False=0
FGIMT
43-2
Pulse
926 bit 8
Uint16 2
R
True=1 False=0
FGIMT
43-2
Reset
926 bit 9
Uint16 2
R
True=1 False=0
FGIMT
43-2
Set
926 bit 10
Uint16 2
R
True=1 False=0
FGIMT
43-2
Output
926 bit 11
Uint16 2
R
True=1 False=0
FGIMT
Reserved
926 bit 12
43-2
Tag Blocking
926 bit 13
Uint16 2
R
True=1 False=0
FGIMT
43-2
Tag Informational
926 bit 14
Uint16 2
R
True=1 False=0
FGIMT
43-2
Untag Blocking
926 bit 15
Uint16 2
R
True=1 False=0
FGIMT
43-2
Untag Informational
927 bit 0
Uint16 2
R
True=1 False=0
FGIMT
43-2
Tag Blocking Status
927 bit 1
Uint16 2
R
True=1 False=0
FGIMT
43-2
Tag Informational Status
927 bit 2
Uint16 2
R
True=1 False=0
FGIMT
43-3
Pulse
927 bit 3
Uint16 2
R
True=1 False=0
FGIMT
43-3
Reset
927 bit 4
Uint16 2
R
True=1 False=0
FGIMT
43-3
Set
927 bit 5
Uint16 2
R
True=1 False=0
FGIMT
43-3
Output
927 bit 6
Uint16 2
R
True=1 False=0
FGIMT
Reserved