Basler Electric BE1-11 Modbus Protocol User Manual
Page 65
9424200774 Rev B
59
BE1-11
Register Table
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
25
Angle
Compensation
SG2
20262
3246*
Float
4
R W
Degree
0 - 359.9
FGI
25
Mode
SG3
20264
3248*
Uint32
4
R W
n/a
Disabled=0
Enabled=1
FGI
Reserved
20266-
67
25
Voltage
Monitor Mode
SG3
20268
3250*
Uint32
4
R W
n/a
Disabled=0
DLDA=1
DLLA=2
DLDA_DLLA=3
LLDA=4
LLDA_DLDA=5
DLLA_LLDA=6
DLDA_DLLA_LLDA=7
FGI
25
Phase Angle
SG3
20270
3252*
Float
4
R W
Degree
1 - 99
FGI
25
Slip Freq
SG3
20272
3254*
Float
4
R W
Hertz
0.01 - 0.5
FGI
25
Volt Mag Error
Percent
SG3
20274
3256*
Float
4
R W
Percent
1 - 50
FGI
25
Vs Fast Vd
SG3
20276
3258*
Uint32
4
R W
n/a
Disabled=0
Enabled=1
FGI
25
Dead Voltage
SG3
20278
3260*
Float
4
R W
Percent
10 - 90
FGI
25
Live Voltage
SG3
20280
3262*
Float
4
R W
Percent
10 - 90
FGI
25
Drop Out
Delay
SG3
20282
3264*
Float
4
R W
Millisecond 50 - 60000
FGI
25
Angle
Compensation
SG3
20284
3266*
Float
4
R W
Degree
0 - 359.9
FGI
27P-1
Mode
SG0
20286
3268*
Uint32
4
R W
n/a
Disabled=0
One of Three=1
Two of Three=2
Three of Three=3
FGIMT
Reserved
20288-
89
27P-1
Timing Mode
SG0
20290
3270*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIMT
27P-1
Pickup
SG0
20292
3272*
Float
4
R W
Volt
1 - 300
FGIMT
27P-1
Time Delay
SG0
20294
3274*
Float
4
R W
Millisecond 50 - 600000
FGIMT
27P-1
Inhibit Level
SG0
20296
3276*
Float
4
R W
Volt
1 - 300
FGIMT
27P-1
Time Multiplier
SG0
20298
3278*
Float
4
R W
n/a
0 - 9.9
FGIMT
27P-1
Mode
SG1
20300
3280*
Uint32
4
R W
n/a
Disabled=0
One of Three=1
Two of Three=2
Three of Three=3
FGIMT
Reserved
20302-
03
27P-1
Timing Mode
SG1
20304
3282*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIMT
27P-1
Pickup
SG1
20306
3284*
Float
4
R W
Volt
1 - 300
FGIMT
27P-1
Time Delay
SG1
20308
3286*
Float
4
R W
Millisecond 50 - 600000
FGIMT
27P-1
Inhibit Level
SG1
20310
3288*
Float
4
R W
Volt
1 - 300
FGIMT
27P-1
Time Multiplier
SG1
20312
3290*
Float
4
R W
n/a
0 - 9.9
FGIMT
27P-1
Mode
SG2
20314
3292*
Uint32
4
R W
n/a
Disabled=0
One of Three=1
Two of Three=2
Three of Three=3
FGIMT
Reserved
20316-
17
27P-1
Timing Mode
SG2
20318
3294*
Uint32
4
R W
n/a
Definite Timing=0
Inverse Timing=1
FGIMT
27P-1
Pickup
SG2
20320
3296*
Float
4
R W
Volt
1 - 300
FGIMT
27P-1
Time Delay
SG2
20322
3298*
Float
4
R W
Millisecond 50 - 600000
FGIMT
27P-1
Inhibit Level
SG2
20324
3300*
Float
4
R W
Volt
1 - 300
FGIMT
27P-1
Time Multiplier
SG2
20326
3302*
Float
4
R W
n/a
0 - 9.9
FGIMT