Basler Electric BE1-11 Modbus Protocol User Manual
Page 81

9424200774 Rev B
75
BE1-11
Register Table
Name
Description
Group Register
Type
Bytes Writable
Unit
Range
Style
50-2
Mode
SG1
21320
4084*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-2
Source
SG1
21322
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-2
Pickup
SG1
21324
4086*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-2
Time Delay
SG1
21326
4088*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-2
Direction
SG1
21328
4090*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-2
Mode
SG2
21330
4092*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-2
Source
SG2
21332
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-2
Pickup
SG2
21334
4094*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-2
Time Delay
SG2
21336
4096*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-2
Direction
SG2
21338
4098*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-2
Mode
SG3
21340
4100*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-2
Source
SG3
21342
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-2
Pickup
SG3
21344
4102*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-2
Time Delay
SG3
21346
4104*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-2
Direction
SG3
21348
4106*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-3
Mode
SG0
21350
4108*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-3
Source
SG0
21352
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-3
Pickup
SG0
21354
4110*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-3
Time Delay
SG0
21356
4112*
Float
4
R W
Millisecond 0 - 60000
FGIMT
50-3
Direction
SG0
21358
4114*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT